Chapter 2 Mechanical Installation 11
DataMate 3000 Series Air Conditioner User Manual
2.4.2 Location Consideration
Note
The DataMate3000 generates water. Water leaks can cause damage to sensitive system
nearby. Do not mount units near sensitive systems. Be sure to install a field-supplied pan
with a drain line.
1. Try to locate the evaporator in a capacious floor space to ensure normal
operation.
2. Avoid locations in confined areas that affect the airflow pattern and result in short
cycles and abnormal noise.
3. Do no install the unit in an alcove or at the extreme end of a long, narrow room.
4. Do no install multiple units close to each other. This can result in crossing air
patterns, uneven loads and competing operating modes.
5. Do not attach additional devices (such as smoke detectors, and so on.) to the
cabinet that will interfere with routine maintenance or service.
Figure 2-5 indicates the recommended room location.
Not recommended
Recommended
location
Not recommended
Recommended
location
Figure 2-5 Recommended room location of evaporator