24 Chapter 3 Electrical Installation
DataMate 3000 Series Air Conditioner User Manual
J18
Custom #1
J6
8
J6
7
Custom #2
Standby unit
enable
J14
Smoking
J22
Fire
J8
Shutdown
J9
Changeover
J10
General
Figure 3-5 Control terminal arrangement
Note
The installation engineer must take anti-static measures before making connection.
3.4.1 Remote Unit Shutdown, Smoking And Fire Sensing
As shown in Figure 3-5, the signals fed to the following terminals are:
J8: Remote on/off control
J14: Smoke alarm
J22: Fire alarm
If these three terminals are shorted and the power switch of the system is switched
on, the air conditioner will run. If any of the three terminals are not shorted, the air
conditioner will stop. In this way, DataMate3000 air conditioner can be shut down
through these terminals in case of emergency.
The three control circuits are shorted through the three terminals before delivery.
Remove the shorting wires if the smoke and fire sensor cables and the remote
on/off control cable are connected to the terminals of J8, J14 and J22 respectively.
3.4.2 Custom Alarms
Terminals J67 (Custom #1) and terminals J68 (Custom #2) can be input with any
external alarm if the unit provides a set of normally open dry contacts. The custom
alarm needs to be set in the controller (refer to section 5.6.5). When the contacts
close, the unit will activate an audible alarm and display the alarm on the LCD. If a
computer is connected using the monitoring software of Emerson, the alarm will
also be raised at the computer.