42 Chapter 5 Microprocessor Control
DataMate 3000 Series Air Conditioner User Manual
5.9.1 System Setup
System settings will not be lost when power fails. Select System Setup from the
System Menu to display the items listed in Figure 5-24.
M
o n i t o r
T e a m w o r k
S t a r t D e l a y
C / F D e g r e e s
H
u m C o n t r o l R E L
B e e p e r O N
B a c k l i g h t O N
C o n t r a s t 3 0 %
Figure 5-24 System Setup sub-menu
Use Up/Down buttons to move the cursor to Monitor as shown in Figure 5-24, and
press Enter to display the sub-menu, as shown in Figure 5-25. Press Enter to set
the system address for communicating with a host. The setting range is 1~244 and
the default value is 1.
U
n i t N o 1
Figure 5-25 Monitor sub-menu
1. Use Up/Down buttons to move the cursor to Teamwork in the System Setup
menu, and press Enter to display the Teamwork sub-menu, as shown in Figure
5-26. Use Up/Down buttons to move the cursor to Cntl Brd, and press Enter to set
the control board number for communication with other control boards. It can be set
from 0 to 15, and the default value is 0. Use Up/Down buttons to move the cursor to
Unit No, and press Enter to set the unit number. It can be set from 0 to 15, and the
default value is 0.
C
n t l B r d 1
U n i t N o 1
Figure 5-26 Teamwork sub-menu
2. Use Up/Down buttons to move the cursor to Start Delay in the System Setup
menu, and press Enter to display the sub-menu, as shown in Figure 5-27. The
default values and the setting ranges of the delays in Figure 5-27 are listed in Table
5-1.