36 Chapter 5 Microprocessor Control
DataMate 3000 Series Air Conditioner User Manual
5.6.1 Alarm Status
Select Alarm Status from the Alarm Menu to enter the Alarm Status screen. This
screen displays all active alarms.
The alarm No/ the total number active, alarm name, the time/date occurrence are
indicated for each alarm, as shown in Figure 5-9.
A
c t i v e : 1 / 4
H i g h T e m p
2 0 0 4 / 0 1 / 0 1 0 0 : 0 0
Figure 5-9 Alarm Status screen
The latest alarm is shown as alarm 1. Use Up/Down buttons to scroll if there are
more alarms.
This system can store up to 15 latest active alarms. They will be lost when the
system is powered off.
5.6.2 Alarm History
Select Alarm History from the Alarm Menu screen to view the Alarm History screen.
The screen displays the detailed inactive alarm information or “No alarms” if no
inactive alarm exists.
The alarm No./the total number inactive, alarm name, the time/date occurrence are
indicated for each alarm, as shown in Figure 5-10.
H
i s t o r y : 1 / 4
H i g h T e m p
0 1 / 0 1 0 0 : 0 0 : 0 0
0 1 / 0 1 0 0 : 0 0 : 0 0
Figure 5-10 Alarm History screen
Use Up/Down buttons to scroll if there are more alarms.
This system can store up to 30 latest inactive alarms. They will not be lost when the
system is powered off.