Chapter 2 Mechanical Installation 25
Liebert.PEX Chilled Water Series Air Conditioner User Manual
2.7 Installation Inspection
After the mechanical installation is completed, you should check that:
1. A certain space is left around the unit for maintenance. For details, see
Maintenance space requirement
in
2.3.1 Installation Requirement
;
2. The equipment is installed vertically and the installation fasteners have been fixed;
3. The pipes connecting the indoor unit and outdoor unit have been connected;
4. The condensate pump (if needed) has been installed;
5. The drain pipe has been connected;
6. The water supply pipe for infrared humidifier has been connected;
7. All pipe joints have been fixed;
8. The transport fasteners have been removed;
9. The water level regulator of the infrared humidifier has been unscrewed to the required height;
10. The debris (such as transportation materials, structure materials and tools) inside or around the
equipment has been cleaned.
After confirming the preceding points, you can then start the electrical installation.