Chapter 5 iCOM Controller 51
Liebert.PEX Chilled Water Series Air Conditioner User Manual
C1 ACT, C2 ACT, C3 ACT and C4 ACT correspond to the customer alarms. ‘OPEN’ means normally open,
‘CLOSE’ means normally closed.
Alarm delays setting
The alarm delays are the time after faults occur and before the alarms are triggered. See Figure 5-9 for the
menu format.
2/10
S236
S237
S238
S239
S240
S241
FOL
LOA
CF
HRT
LRT
HRH
DEL
EN
T
5
3
2
30
30
30
Yes
Yes
Yes
Yes
Yes
Yes
ALM
ALM
WRN
WRN
WRN
WRN
01
SET ALARMS
Figure 5-9 Alarm delay
The alarm name, delay time, delay enabling and alarm type are displayed from left to right in the list.
The alarm delay can be set to 0 ~ 9999. Unit: second.
The delay enabling determines whether the alarm will be displayed and the alarm menu is entered, Options
include ‘Yes’ and ‘No’.
The alarm type can be set to ‘ALM’ (alarm), ‘WRN’ (warning) and ‘MSG’ (message). They determine the alarm
degree of the corresponding event.
The alarm names are listed in Table 5-25.
Table 5-25 Alarm name description
SN
Alarm/event
name
Description
SN
Alarm/event
name
Description
S236
FOL
Fan overload
S266
LOF
Loss of flow
S237
LOA
Loss of airflow
S267
SGP
Standby glycol pump on
S238
CF
Filter clogged
S268
STB
Standby unit on
S239
HRT
High room temp.
S269
HUP
Humidifier problem
S240
LRT
Low room temp.
S270
NOC
No connection w/Unit1
S241
HRH
High room hum.
S271
-
No connection w/UnitX
S242
LRH
Low room hum.
S272
LOP
LOSS OF POWER
S243
HTA
High temperature of sensor A
S275
CI1
Customized input 1
S244
LTA
Low temperature of sensor A
S276
CI2
Customized input 2
S245
HHA
High humidity of sensor A
S277
CI3
Customized input 3
S246
LHA
Low humidity of sensor A
S278
CI4
Customized input 4
S249
OL1
Compressor 1 overload
S279
CS
Call for service
S250
OL2
Compressor 2 overload
S280
HTD
High temperature
S251
HP1
Compressor 1 high pressure
S281
LB1
Loss of air blower 2
S252
HP2
Compressor 2 high pressure
S282
RL
Reheat lockout
S253
LP1
Compressor 1 low pressure
S283
HL
Humidifier lockout
S254
LP2
Compressor 2 low pressure
S284
FCL
FC lockout
S255 PD1
Compressor 1 pumpdown
fails
S285 CL Compressor(s)
lockout
S256 PD2
Compressor 2 pumpdown
fails
S288
SC1
Short cycle 1
S257 HT1
Digital scroll 1 high
temperature
S289
SC2
Short cycle 2
S258 HT2
Digital scroll 2 high
temperature
S290 NOP NO
power
S259
EHO
EL HEAT HIGH TEMP
S291
CN1
Condensor 1 Fail
S262
WHE
Working hours exceeded
S292
CN2
Condensor 2 Fail
S263
SMO
Smoke detected
S293
EFF
EC Fan fail
S264
WUF
Water under floor
S294
HST
High supply air temperature
S265
CPH
Conderser pump high water
S295
LST
Low supply air temperature