52 Chapter 5 iCOM Controller
Liebert.PEX Chilled Water Series Air Conditioner User Manual
5.7.7 CALIBRATION
The CALIBRATION menu can calibrate sensors by setting offsets. The parameters are listed in Table 5-26. The
parameters are in pairs: the former is the calibrated value and the latter is the calculated value, or the sum of
the measured value and the calibrated value. This value is engaged in the calculation of control need.
Table 5-26 Descriptions of CALIBRATION parameters
Parameters
Default
Description
S602 RTN TEMP K
Calibrated return air temperature. It can be set as a positive or negative value. Use
the up and down buttons to change the setting value, 0.1K at each step
S603 CAL TEMP 25°C
Sum of the calibrated value and measured return air temperature. This value is
compared with the setting value as the system actual temperature and is engaged in
the calculation
S604 RTN HUM
+0.0%
Calibrated return air humidity. It can be set as a positive or negative value. Use the
up and down buttons to change the setting value, 1% at each step
S605 CAL HUM
44.0%
Sum of the calibrated value and measured return air humidity. This value is
compared with the setting value as the system actual humidity and is engaged in
the calculation
S606 DS1 NTC
+0.0K
Calibrated digital scroll 1NTC. It can be set as a positive or negative or positive
value. Use the up and down buttons to change the setting value, 0.1K at each step
S607 CAL DS1
29°C
Sum of the calibrated value and return air humidity measured by digital scroll 1NTC
sensor. This value is engaged in the calculation
S608 DS2 NTC
+0.0K
Calibrated digital scroll 2NTC. It can be set as a positive or negative value. Use the
up and down buttons to change the setting value, 0.1K at each step
S609 CAL DS2
25°C
Sum of the calibrated value and return air humidity measured by digital scroll 2NTC
sensor. This value is engaged in the calculation
S610
OUT SNS
°C
Outdoor Sensor
S611
CAL OUT
+0.0K
Calibrated Outdoor Sensor
S613
TEMP A
+0.0K
Calibrated value of temperature sensor A
S614
CAL A
°C
Calculated value corresponding to temperature sensor A
S615
HUM A
+0.0%
Calibrated value of humidity sensor A
S616
CAL A
44.0%
Calculated value corresponding to humidity sensor A
S617
TEMP B
TH
Calibrated value of temperature sensor B
S618
TYPE B
+0.0K
Type of temperature sensor B
S619
CAL B
°C
Calculated value corresponding to temperature sensor B
S620
HUM B
+0.0%
Calibrated value of humidity sensor B
S621
CAL B
44.0%
Calculated value corresponding to humidity sensor B
S622
TYPE C
TH
Type of temperature sensor C
S624 FC SNSR
-
Free cooling temperature sensor. PTC or NTC sensor can be configured according
to the actual configuration
S625
FC SNSR
+0°C
Calibrated value of free cooling temperature sensor
S626
CAL FC
°C
Calculated value of free cooling temperature sensor
S627
SUP SNSR
NTC
Air supply temperature sensor. PTC or NTC sensor can be configured
S628
SUP TEMP
+0.0K
Calibrated value of air supply temperature sensor
S629
CAL SUP
°C
Calculated value of air supply temperature sensor
S630
TEMP C
+0.0K
Calibrated value of temperature sensor C
S631
CAL C
°C
Calculated value of temperature sensor C
S632
HUM C
+0.0%
Calibrated value of humidity sensor C
S633
CAL C
%
Calculated value of humidity sensor C
5.7.8 NETWORK SETUP
The NETWORK SETUP menu is used to set the parameters when the system is in a network subject to the
monitoring of a host. See Table 5-27 for parameter descriptions.
Table 5-27 Descriptions of NETWORK SETUP parameters
Parameters
Default
Setting
range
Description
S802
#UNITS
1
1 ~ 32
Range: 1 ~ 32
S803
TEAMWORK
No
No, 1, 2
Range: No, 1, 2