72 Chapter 6 Application Of INTELLISLOT
Liebert.PEX Chilled Water Series Air Conditioner User Manual
3. Click the Access on SNMP at the left hand of the interface, as shown in Figure 6-11. Type user name
‘Liebert’ and password ‘Liebert’ and click the OK button to enter the setting interface of configure. Note that
the user name and password are case-sensitive.
Password
Username
OK
Cancel
Connect to
Figure 6-11 Typing user name and password
4. Configure the Network Management System (NMS) of the host monitoring center in Figure 6-12. Click the
Edit button and type the IP address of the NMS in IP Address. Select the ‘read’ or ‘write’ in Access, type
‘Public’ in Community and then click the Save button.
Note
1. Before setting the NMS, the
Edit
button is displayed in the interface. After editing the configuration, the
Edit
button will
become the
Save
button.
2. After the NMS is configured, you must click the
Save
button to save the setting.
Figure 6-12 NMS configuration interface of SNMP host monitoring center (1)