Connecting the CH Breaker Gateway to the Breaker Panels
Networking • 3
4
Networking
4.1.
Connecting the CH Breaker
Gateway to the Breaker Pan-
els
The Cutler-Hammer breaker panels connect to the
Gateway by MODBUS network connection. MODBUS is
a two-wire, polarity-sensitive network physically similar to
RS485. Using shielded, two-conductor 22AWG wire
(Belden #8761 or equivalent), connect all panels in a single
daisy-chain network configuration leading from the Gate-
way to each of the breaker panels in series.
Figure 4-1
shows how to connect the wires to the
MODBUS connectors.
IMPORTANT!
The polarity of the PRC100MOD con-
nectors is the opposite of the Gateway board’s connector.
The wire color connected to the positive (+) terminal of the
Gateway board should be wired to the negative (-) terminal
on the breaker panels, and vice-versa.
4.1.1. Terminating the MODBUS Net-
work
The two devices at the ends of the MODBUS network
must be terminated. If the Gateway board is one of the end
devices, terminate the network using the three termination
jumpers located next to the Gateway MODBUS Connector
(
Figure 4-2
). PRC100MOD boards have no on-board ter-
mination and must be terminated with a 150-ohm resistor
across the + and - terminals
(Figure 4-2)
.
4.1.2. Setting the PRC100MOD Address
The PRC100MOD controllers on the Cutler-Hammer
breaker panels have a switch used to set the MODBUS ad-
dress. This switch must be used to give each PRC100MOD
a unique address from 1 through 4.
Figure 4-3
shows the
switch location and positions for each MODBUS address.
Figure 4-1
- MODBUS Connection Diagram
PRC100MOD
PRC100MOD
Gateway
Board
MODBUS
CONNECTOR
MODBUS
CONNECTORS
- (BLACK)
+ (WHITE)
0V (SHIELD)
GATEWAY
MODBUS
CONNECTOR
0V (SHIELD)
0V (SHIELD)
+ (BLACK)
- (WHITE)
+ (BLACK)
- (WHITE)
PRC 100
MODBUS
CONNECTORS
NOTE: POLARITY
ON PRC 100
MODBUS
CONNECTORS
IS THE INVERSE
OF THE GATEWAY
WIRE + on Gateway
to - on PRC100s
WIRE - on Gateway
to + on PRC100s
Figure 4-2
- MODBUS Network Termination
Figure 4-3
- MODBUS Addressing Switch Positions
PRC100MOD
PRC100MOD
Gateway
Board
TERMINATION
TERMINATION
NO
TERMINATION
TERMINATION
150
Ω
PRC100MOD
PRC100MOD
Gateway
Board
MODBUS
CONNECTOR
MODBUS
CONNECTORS
- (BLACK)
+ (WHITE)
0V (SHIELD)
GATEWAY
MODBUS
CONNECTOR
0V (SHIELD)
0V (SHIELD)
+ (BLACK)
- (WHITE)
+ (BLACK)
- (WHITE)
PRC 100
MODBUS
CONNECTORS
NOTE: POLARITY
ON PRC 100
MODBUS
CONNECTORS
IS THE INVERSE
OF THE GATEWAY
WIRE + on Gateway
to - on PRC100s
WIRE - on Gateway
to + on PRC100s