REFLECS
Site Controller Software Setup • 5
4.2.3. Setting the RS485 I/O Termi-
nation Jumpers
As part of a site controller’s RS485 I/O (COM A or
COM D) Network, a Gateway must be terminated if it is the
end device of a daisy chain. Refer to the controller’s user
manual for information about daisy chain networks and
how they are terminated.
To terminate the Gateway, set the I/O Network Jumpers
to the RIGHT position as shown in
Figure 4-8
. To unter-
minate the Gateway, set the jumpers to the LEFT position.
5
Site Controller Soft-
ware Setup
5.1.
REFLECS
For backwards compatibility with REFLECS, the CH
Breaker Gateway behaves on the network identically to
16AI and 8RO boards. These devices should be set up and
addressed in the same way I/O boards are set up. Refer to
your controller’s manual for set up instructions.
5.2.
E2 and Einstein
5.2.1. Board and Application Setup
Set up the number of boards on the I/O Network from
the Connected I/O screen. Press the
I
key to open the
Main Menu and press:
1.
System Configuration
2.
Network Setup
3.
Connected I/O Boards and Controllers
If using an Einstein controller, from the Main Status/
Home screen, press
(
(Actions),
Network Status/
Setup, and then
Connected I/O Boards & Controllers.
Add as many 16AIs and 8ROs as is necessary to cover
the entire Start-End range chosen in
Section 4.2.1.,
Gate-
way Board Numbering
. Press
J
to save and exit.
Figure 4-7
- Dip Switch Setting for Numbering Gateway
Figure 4-8
- Gateway RS485 I/O Network Termination
GATEWAY
DIP SWITCH
I/O NETWORK OR
COM A AND D
BAUD RATE
I/O NET BAUD RATE SETTINGS
2
3
4
5
6
7
8
1
9600
19200
Figure 5-1
- Connected I/O Boards Screen