February 2019
User Instructions
MAN-02-04-60-0350-EN Rev. 3
51
Section 7: Parameter Menu
Parameter Menu
7.11
Parameter Group: Step Mode
Step mode operation can be used to extend the operating time in certain ranges or for the
whole travel; it is available in local, remote and emergency mode.
Step mode operation can be activated individually for the directions OPEN and CLOSED.
Cycle start, cycle end, cycle duration and interval time can be set separately for both
directions. (see capter Figure 52).
Table 18.
Step Mode Parameter Group
Menu Item
Sub Menu
Item
Poss.
Setting
Notes / Comments
P12.1
Step mode
function
Mode
disabled
Step mode operation is disabled
enabled
Step mode operation is enabled in LOCAL, REMOTE
and EMERGENCY operation
Local only
Step mode mode is only enabled in LOCAL mode
Remote
only
Step mode mode is only enabled in REMOTE mode
Local +
Remote
only
Step mode mode is enabled in REMOTE and LOCAL mode
P12.2
Step mode
function
Start Open
0 - 100%
In OPEN direction, position in % from which the step
mode operation should start
P12.3
Step mode
function
End Open
0 - 100%
In OPEN direction, position in % of which the step mode
operation should end
P12.4
Step mode
function
Runtime Open 0,1 - 60
Runtime in OPEN direction
P12.5
Step mode
function
Pause time
Open
0,2 - 60
Pause time in OPEN direction
P12.6
Step mode
function
Start Closed
0 - 100%
In CLOSED direction, position in % from which the step
mode operation should start
P12.7
Step mode
function
End Closed
0 - 100%
In CLOSED direction, position in % of which the step
mode operation should end
P12.8
Step mode
function
Run time
Closed
0,1 - 60
Runtime in Closed direction
P12.9
Step mode
function
Pause time
0,2 - 60
Pause time in Closed direction
P12.10
Step mode
function
Timebase
{0:
Seconds}
Time basis for run and pause times
1: Minutes
P12.11
Step mode
function
Speed
adaption
0:
Speed adaption not activated. Normal step mode function
1:
Speed adaption is activated. The speed is reduced
according to the runtime and pause time in the step
mode range. (Example: Running time 1 sec and pause
time 1 sec results in half the speed). If the minimum
speed is undershot, the actuator clocks in the converted
ratio with the minimum speed. The speed adjustment is
only applicable to actuators of the type CM and AB CSC