Section 7: Parameter Menu
Parameter Menu
7.5
Parameter Group: Control
Table 8.
Control Parameter Group
Menu Item
Sub Menu
Item
Poss.
Setting
Notes / Comments
P6.2
Control
Ready delay
0 - 10 sec. Drop-out delay for the ready signal (Binary outputs)
P6.5
3)
Control
24V output
0
24V auxiliary output is deactivated (section 16.5)
The function of the auxiliary input is still activated
{1}
24V auxiliary output is activated (section 16.5)
P6.6
Control
Min. impuls
0.1 - 2.0
sec
Minimum switch-on time of the motor
3)
since firmware 1.303
7.6
Parameter Group: Password
The actuator control can be password-protected to prevent access at different levels. It is
possible to prevent entry by unauthorized personnel or to entirely lock motor operation.
Default password is set to "000" and thus deactivated.
You can use both numbers and capital letters in your password. After entering a password,
password protection is acti- vated. To remove password protection, enter an empty
password (000).
When accessing a password-protected parameter, the user is automatically prompted for
its introduction. Only after cor- rectly entering the password, it is possible to change the
corresponding parameters.
Table 9.
Password Parameter Group
Menu Item
Sub Menu
Item
Poss.
Setting
Notes / Comments
P7.1
Password
Reading PWD 3-digit
Status display and history data are still viewable; access
to the parameter menu is locked until this password is
introduced. Parameter menu scrolling is only enabled
after entering the password. Electric motor operation is
unlocked.
P7.2
Password
Writing PWD
3-digit
Status display, history data and parameter menu can be
viewed. However, parameters become read-only.
P7.3
Password
Bluetooth
PWD
15-digit
Password for the Bluetooth connection, empty password
deactivates the password request.