SI-I/O User Guide
Issue Number: 3
This parameter displays the current status of the module. All possible values are shown in the table below.
Changes to the module's configuration will not take effect until the module has been reset.
•
To reset the module:
•
Set Pr
S.00.007
to On (1).
•
When the sequence has been completed, Pr
S.00.007
will be reset to Off (0).
The module will reset using the updated configuration.
This sequence does NOT store the module's configuration parameters in the drive or the module's flash memory. This parameter will change back to
Off immediately, and as such the change may not be visible in the display.
If the host drive is defaulted (see the drive user guide for details), it will also clear the current configuration for the slot the module is installed to.
This can be performed as follows:
•
Set Pr
S.00.008
to On.
•
Reset the module by setting Pr
S.00.007
to On.
•
Default parameter values for the module will be loaded.
The module will reset using the default values.
This parameter shows the slot number that the module is installed in.
S.00.006
Module Status
Minimum
0
Maximum
101
Default
Units
Type
8 Bit Volatile
Update Rate
Background read
Display Format
None
Decimal Places
0
Coding
RO, TE, ND, NC, PT
Value
Text
Description
0
Initializing
Module is currently initializing.
1
Ok
Module has initialized and has found no errors.
2
Config
A configuration error has been detected in one of the
communications protocols or user program
3
Error
An error has occurred preventing the firmware or user program
from running correctly.
100
Bootloader The bootloader is currently running.
101
Updating
The bootloader is currently performing a firmware update. The
power must not be turned off in this state.
S.00.007
Reset Module
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit Volatile
Update Rate
Read every 200 ms
Display Format
None
Decimal Places
0
Coding
RW, NC
NOTE
S.00.008
Default Module
Minimum
0
Maximum
1
Default
0
Units
Type
1 Bit Volatile
Update Rate
Read every 200 ms
Display Format
None
Decimal Places
0
Coding
RW, NC
S.00.030
Slot Indicator
Minimum
0
Maximum
8
Default
Units
Type
8 Bit Volatile
Update Rate
Written on power-up
Display Format
None
Decimal Places
0
Coding
RO, ND, NC, PT, BU