Basic parameters (Menu 0)
Menu 0 is used to bring together various commonly used parameters for basic easy set up of the
drive. All the parameters in Menu 0 appear in other menus in the drive (denoted by {…}). Menus 22
can be used to configure the parameters in Menu 0.
6.1 Menu 0: Basic parameters
Parameter
Range
(
Ú
)
Default
(
Ö
)
Type
OL
RFC-A
OL
RFC-A
00.001
Minimum Reference
Clamp
±VM_NEGATIVE_REF_CLAMP1 Hz
0.00 Hz
RW Num
US
00.002
Maximum Reference
Clamp
±VM_POSITIVE_REF_CLAMP Hz
50Hz default: 50.00 Hz
60Hz default: 60.00 Hz
RW Num
US
00.003
Acceleration Rate 1
±VM_ACCEL_RATE s/100 Hz
5.0 s/100 Hz
RW Num
US
00.004
Deceleration Rate 1
±VM_ACCEL_RATE s/100 Hz
10.0 s/100 Hz
RW Num
US
00.005
Drive Configuration
AV (0), AI (1), AV.Pr (2), AI.Pr (3),
Preset (4), Pad (5), Pad.Ref (6),
E.Pot (7), torque (8), Pid (9)
AV (0)*
RW
Txt
PT US
00.006
Motor Rated Current
0.00 to VM_RATED_CURRENT A
Maximum Heavy Duty
Rating A
RW Num
RA
US
00.007
Motor Rated Speed
0.0 to 80000.0 rpm
50Hz default:
1500.0 rpm
60Hz default:
1800.0 rpm
50Hz default:
1450.0 rpm
60Hz default:
1750.0 rpm
RW Num
US
00.008
Motor Rated Voltage
0 to VM_AC_VOLTAGE_SET V
110V drive: 230 V
200V drive: 230 V
400V drive 50 Hz: 400 V
400V drive 60 Hz: 460 V
RW Num
RA
US
00.009
Motor Rated Power
Factor
0.00 to 1.00
0.85
RW Num
RA
US
00.010
User Security Status
LEVEL.0 (0), ALL (1), r.only.0 (2),
r.only.A (3), Status (4), no.acc(5)
LEVEL.0 (0)
RW Num ND NC PT
00.015
Jog Reference
0.00 to 300.00 Hz
1.50 Hz
RW Num
US
00.016
Analog Input 1 Mode
4-20.S (-6), 20-4.S (-5),
4-20.L (-4), 20-4.L (-3),
4-20.H (-2), 20-4.H (-1), 0-20 (0), 20-
0 (1), 4-20.tr (2), 20-4.tr (3),
4-20 (4), 20-4 (5), Volt (6)
Volt (6)
RW
Txt
US
00.017
Bipolar Reference
Enable
Off (0) or On (1)
Off (0)
RW
Bit
US
00.018
Preset Reference 1
±VM_SPEED_FREQ_REF Hz
0.00 Hz
RW Num
US
00.025
User Security Code
0 to 9999
0
RW Num ND NC PT US
00.027
Power-up Keypad
Control Mode
Reference
Reset (0), Last (1), Preset (2)
Reset (0)
RW
Txt
US
00.028
Ramp Mode Select
Fast (0), Std (1), Std.bst (2),
Fst.bst (3)
Std (1)
RW
Txt
US
00.029
Ramp Enable
Off (0) or On (1)
On (1)
RW
Bit
US
00.030
Parameter Cloning
None (0), rEAd (1), Prog (2),
Auto (3), boot (4)
None (0)
RW
Txt
NC
US
00.031
Stop Mode
CoASt (0), rP (1), rP.dc I (2),
dc I (3), td.dc I (4), dis (5),
No.rP (6)
rp (1)
RW
Txt
US
00.032
Dynamic V to F
Select / Flux
Optimization Select
0 to 1
0
RW Num
US
Unidrive M200 201 Quick Start Guide English Iss6.book Page 27 Thursday, September 10, 2015 1:48 PM