53
COMPRESSOR MODEL
Sound Power
(dBA)
Sound Power
with Noise jacket
(dBA)
Maximum
Running
Sound
(dBA)
MBP
LBP
50Hz
60Hz
50Hz
60Hz
SE6015-SE6021
SE2006-SE2010
71
73
68
70
75
SE6026-SE6036
SE2012-SE2017
73
75
70
72
77
SE6043
SE2020
74
76
71
73
78
SE6053-SE6056
SE2023
75
77
69
71
76
SE6067-SE6078
SE2028-2031
76
78
70
72
77
SE6085-SE6089
SE2039
77
79
71
73
78
Table
11.9 Compressor sound level
Note: Tested in Rated condition of EN12900
11.10 SOUND GENERATION IN REFRIGERATION SYSTEM
Noise and vibrations coming from system or service may come from these sources:
• sound radiation – extend by air
• mechanical vibrations – extended along the parts of the unit and
structure
• gas pulsation – distributed by cooling medium (refrigerant)
The replacement of a compressor is an onerous task and requires an accurate diagnosis of the system
before deciding to proceed with it.
Improper procedures to remove the failed compressor and install a new one, may
cause injury to person, release of refrigerants and oil to the environment, fire and
damages to propriety.
When repairing a refrigeration system, replacing a compressor and installing a new
ones, follow all applicable international regulation and standards (like EN 378-4 or
similar), and the local ones, as well as the safety warnings and recommendations
indicated in these installation instructions.
The compressor replacement must be carried out in properly ventilated ambient.
Disconnect the system from the electrical power.
WARNING
WARNING
WARNING
12. MAINTENANCE
(COMPRESSOR REMOVAL AND REPLACEMENT)