Technical data and dimension diagrams
34
Operating instructions RHF
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
6.5 Rating values
Device series
RHF
380V
RHF
400V
RHF
460V
RHF
500V
RHF
600V
RHF
690V
Nominal range of
the line-to-line line
voltage
U
N
[V]
380
380
≤
U
N
≤
415
440
≤
U
N
≤
480
500
600
690
Tolerance of the
line-to-line line
voltage
U
N
[V]
342
≤
U
N
≤
418
342
≤
U
N
≤
456
396
≤
U
N
≤
528
450
≤
U
N
≤
550
540
≤
U
N
≤
660
540
≤
U
N
≤
759
Power frequency
f
N
[Hz]
60
±
2 %
50
±
2 %
60
±
2 %
50
±
2 %
60
±
2 %
50
±
2 %
Overload ability
1,5
* Efficiency
η
[%]
ca. 98,5-99,5
** THD I
[%]
5-16
cos
ϕ
at 75% I
N
0,85 cap.
at 100% I
N
0,99 cap.
at 150% I
N
1,0 cap.
*
Cooling air
requirement
m³ / h
a) Installation size X1-X2: 200 m³ / h
b) Installation size X3-X6: 350 m³ / h
c) Installation size X7-X8: 700 m³ / h
Power reduction
[%/K]
[%/m]
See figure 7
1000m üNN < h
≤
4000m üNN
⇒
5%/1000m
Table 10: Rating values
* Depended on the device type and design
** At observation of the following connecting conditions: THD U < 2%, standard con-
formable electrical networks