7 Installation
7.1 Mechanical installation
Important information
•
Use the filter modules only as built-in type!
•
Observe the free space of the installation!
–
Several filter modules in one electrical enclosure can be mounted without
clearance side by side.
–
Observe 150mm free space above- and below (see figure 24).
•
The natural convection must not be constrained.
•
At polluted convection (dust, fibrous material, fat, aggressive gases), which
could affect the function of the filter module:
– Make adequate retaliatory actions, for example separate airflow, mounting of fil-
ter modules, regular cleaning, etc.
•
Do not exceed the admissible range of the operating- ambient temperature.
REVCON
®
RHF
150mm
150mm
Figure 24: 150mm free space above and below