Technical data and dimension diagrams
44
Operating instructions RHF
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
Nominal voltage 600V 60Hz
REVCON
®
- type
RHF-A-
Configuration
filter module
Weight
[kg]
Torque*
[Nm]
Clamps X1+X2
Grounding
Cable
cross
section
[mm²]
Cable Lug**
15-600-60-20 A
X3
12
2,4
M8
1,5-25
CS
20-600-60-20 A
X3
13
2,4
M8
1,5-25
CS
24-600-60-20 A
X3
22
2,4
M8
1,5-25
CS
29-600-60-20 A
X4
36
4.5
M8
2,5-50
CS
36-600-60-20 A
X4
40
4.5
M8
2,5-50
CS
50-600-60-20 A
X5
42
6,0
M8
10-70
CS
58-600-60-20 A
X5
52
6,0
M8
10-70
CS
77-600-60-20 A
X6
56
12,0
M8
2,5-95
CS
87-600-60-20 A
X6
62
12,0
M8
2,5-95
CS
109-600-60-20 A
X6
74
12,0
M8
2,5-95
CS
128-600-60-20 A
X6
85
12,0
M8
2,5-95
CL M8
155-600-60-20 A
X7
105
60,0
M12
25-300
CL M8
197-600-60-20 A
X7
123
60,0
M12
25-300
CL M16
240-600-60-20 A
X8
136
60,0
M12
25-300
CL M16
296-600-60-20 A
X8
142
60,0
M12
25-300
CL M16
366-600-60-20 A
X8
163
60,0
M12
25-300
CL M16
395-600-60-20 A
X8
185
60,0
M12
25-300
CL M16
Table 25: Electrical operating conditions 600V 60Hz RHF-A
Nominal voltage 600V 60Hz
REVCON
®
- type
RHF-B-
Configuration
filter module
Weight
[kg]
Torque*
[Nm]
Clamps X1+X2
Grounding
Cable
cross
section
[mm²]
Cable Lug**
15-600-60-20 A
X3
16
2,4
M8
1,5-25
CS
20-600-60-20 A
X3
20
2,4
M8
1,5-25
CS
24-600-60-20 A
X3
38
2,4
M8
1,5-25
CS
29-600-60-20 A
X4
50
4.5
M8
2,5-50
CS
36-600-60-20 A
X4
52
4.5
M8
2,5-50
CS
50-600-60-20 A
X5
75
6,0
M8
10-70
CS
58-600-60-20 A
X5
82
6,0
M8
10-70
CS
77-600-60-20 A
X6
96
12,0
M8
2,5-95
CL M8
87-600-60-20 A
X6
104
12,0
M8
2,5-95
CL M8
109-600-60-20 A
X6
130
12,0
M8
2,5-95
CL M8
128-600-60-20 A
X6
135
12,0
M8
2,5-95
CL M8
155-600-60-20 A
X7
168
60,0
M12
25-300
CL M8
197-600-60-20 A
X7
197
60,0
M12
25-300
CL M16
240-600-60-20 A
X8
220
60,0
M12
25-300
CL M16
296-600-60-20 A
X8
228
60,0
M12
25-300
CL M16
Table 26: Electrical operating conditions 600V 60Hz RHF-B
* Locking torque of the electrical network and converter terminal clamp
** CS
≙
Cable end sleeve, CL
≙
Cable lug