LIMITER
The controller can also be used as a limiter. If the actual value
of the heating circuit exceeds the set limit value, the limiter
switches off the heating circuit (via the safety relay) and locks
it. In order for the heating circuit to be unlocked again, the
actual value must first fall below the limit value. In addition,
the unlocking must be confirmed on the limiter (with DigIn2
or by pressing„ “ for 5 seconds).
The set limit value may only exist as a fixed setpoint, so the
only options are an external setpoint or setpoint W1.
Structure switch settings
No.
description
selection option
S01
Selection actual
value 1 (X1)
[1] = Pt100, 3-wire (AE1)
2 = Pt100, 2-wire (AE1)
3 = thermocouple type J (AE1)
4 = thermocouple type K (AE1)
5 = voltage input (AE3)
6 = current input (AE3)
S03
Select setpoint W
[1] = fixed value W1
S04
Selection of output
function controller
5 = limiter
S06
Alarm:
temperature
absolute – relative
[1] = absolute
2 = relative
S07
Select controller
release (DigIn1)
[1] = continuously
2 = external
Parameters used
No. description
factory
setting
Own
setting
P01 Input variable 1 (X1)
Display only
P03 Reference variable (W)
Display only
P04 current display
Display only
P11 Switching hysteresis 1
2
P12 min. standstill time K1
0
P13 Largest settable setpoint 1
950
P14 Smallest settable setpoint 1
-50
P15 Sensor correction 1
0
P16 Over temperature alarm 1
999
P17 Under temperature alarm 1
-99
P28
Current monitoring load out-
put
0