DESCRIPTION AND TECHNICAL DATA
DESCRIPTION
Temperature controller for heating applications such as
heating cables in industrial plants, with additional alarm relay.
Design for DIN rail mounting. Temperature sensor Pt100 in
3- or 2-wire technology, thermocouples type J, thermocouple
type K or standard signals (0/2V - 10V, 0/4mA - 20mA). Many
different control functions.
Operating status LEDs
LED 1 = operation (heating on)
LED 2 = ramp mode
LED 3 = signaling relay (alarm 2)
LED 4 = alarm relay (alarm 1)
Soft start
When using the internal hybrid relay as a switching output, a
soft start phase is initiated for 20 seconds before each cold start
of the load relay (with 14% power via triac output) in order to
reduce the starting current.
Digital inputs
DigIn1 is used with structure switch position S07 – 2 (external
controller release) and serves as an external release of the load
output.
DigIn2 is used with the structure switch position S04 - 5 (limiter
function) and serves as an external unlocking.
DigIn3 is used with structure switch position S03 – 6 (W1/W2
switchover) and is used to switch between W1 and W2.
Dimensions ELTC-MV2
TECHNICAL SPECIFICATIONS
contoller type
ELTC-MV2
operating voltage
100V..277VAC, +/-10%,
50/60Hz, 24VDC, +/-5%
power consumption
max. 5,5 W
Relay K1
20A res./ max 277 VAC
Relay K2 and K3
8A res. / max. 250 VAC
1A res. / 24 VDC
operating temperature
-25...+55°C
storage temperature
-30...+60°C
adjustment range
-50…+950°C, configurable
display range/ resolution
-50...+999°C
accuracy
± 1K, ± 2 Digits (-50..400°C)
Display / relay indicator
LED, rot, 11mm, three digits
terminals
sensor: 0,2…1,5mm²
copper line
others: 0,1…2,5mm²
solid copper,
stripping length 5…6mm
sensor connection
Pt100 2- or 3-wire,
thermocouples J or K, stan-
dard signal;
meets requirements for
operation with
ELTF PTEx sensors
interface
RS485
attachment
TS35
Protection class
IP20
P
1 2 3 4
ELTC-MV2
www.eltherm.com
153 mm (6.02 in)
47 mm (1.85 in)
63 mm (2.48 in)
93 mm (3.66 in)