STRUCTURE SWITCHES AND THEIR MEANING
There are 9 structure switches (S01 to S09) with a different
number of switch positions. Each structure switch is assigned
a function with at least two or more alternatives, which are
selected using only one possible switch position per structure
switch.
P45: Medium-selection
1
Water, brine, caustic soda
2
Water-based liquid, acids, alkalis
3
Liquid hydrocarbons, vegetable oils
4
Gases
5
Other
P47: Metal pipe size
1
3 mm
1/8"
17
200 mm
8"
2
6 mm
1/4"
18
225 mm
9"
3
10 mm
3/8"
19
250 mm
10"
4
15 mm
1/2"
20
300 mm
12"
5
20 mm
3/4"
21
350 mm
14"
6
25 mm
1"
22
400 mm
16"
7
32 mm
1 1/4"
23
450 mm
18"
8
40 mm
1 1/2"
24
500 mm
20"
9
50 mm
2"
25
550 mm
22"
10
65 mm
2 1/2"
26
600 mm
24"
11
80 mm
3"
27
650 mm
26"
12
90 mm
3 1/2"
28
700 mm
28"
13
100 mm
4"
29
750 mm
30"
14
125 mm
5"
30
800 mm
32"
15
150 mm
6"
31
850 mm
34"
16
175 mm
7"
32
900 mm
36"
P48: Plastic pipe size
1
10 mm
3/8"
10
75 mm
2 7/8"
2
12 mm
3/8+"
11
100 mm
4"
3
15 mm
1/2"
12
125 mm
5"
4
20 mm
3/4"
13
150 mm
6"
5
25 mm
1"
14
200 mm
8"
6
32 mm
1 1/4"
15
250 mm
10"
7
40 mm
1 1/2"
16
300 mm
12"
8
50 mm
2"
17
400 mm
16"
9
65 mm
2 1/2"
no.
meaning
S01
Selection actual value
X1
[1] = Pt100, 3-wire (AE1)
2 = Pt100, 2-wire (AE1)
3 = Thermocouple type J (AE1)
4 = Thermocouple type K (AE1)
5 = Voltage input (AE3)
6 = Current input (AE3)
S02
Selection actual value
X2
[0] = Input disabled
1 = Pt100, 3-wire (AE2)
2 = Pt100, 2-wire (AE2)
3 = Thermocouple type J (AE2)
4 = Thermocouple type K (AE2)
5 = Voltage input (AE4)
6 = Current input (AE4)
S03
Select setpoint W
[1] = Fixed value W1
2 = Fixed value W2
3 = Ramp function
4 = Sliding setpoint (W2+X2)
5 = External setpoint (AE4)
6 = Changeover W1/W2 (DigIn 3)
S04
Selection of output
function controller
[1] = two-point control
2 = pulse width modulation (PWM)
3 = proportional control
4 = continuous control
5 = limiter
S05
Selection switching
output
[1] = internal hybrid relay with soft
start
2 = external power contactor
3 = analog output clocked
S06
Alarm selection:
temperature absolute
– relative
[1] = absolute
2 = relative
S07
Select controller
release (DigIn1)
[1] = continuously
2 = external
S08
Alarm relay mode
1 = alarm relay on in case of error
[2] = alarm relay off on error
3 = enable relay mode
4 = like 0, but heating on
5 = like 1, but heating on
6 = like 2, but heating on
S09
Selection of display
format
[1] = °C
2 = °F