9
Installation and commissioning
Smoke alarm Salva KNX
• Version: 09.09.2016 • Technical Changes and Errors excepted.
Small rooms
: If the minimum distance to the wall cannot be maintained, install the
alarm on the wall. Keep a distance of at least 0.50 m and maximum 1 m to the ceiling.
Rooms with a gallery
: Attach an additional alarm underneath the gallery if said gal-
lery is longer and wider than 2 m and has more than 16 m².
Segmented ceilings
: If there are separate areas in the ceiling with a depth of more
than 0.20 m and an area of more than 32 m² (e.g. due to beams separating the areas),
install an alarm in each area (on the ceiling or on the beams).
The device is only approved for interior spaces. Do not install in rooms
with temperatures of less than -10°C or more than +50°C! Avoid
condensation.
Do not install in rooms in which a high degree of water vapour is
produced under normal circumstances (e.g. kitchen, bathroom, toilet)!
Do not install near places of fire or open fireplaces!
Do not install near ventilation shafts (e.g. of air conditioning or
circulating air systems)!
Attach the first alarm at a maximum distance
of 7.50 m to the end of the room in long struc-
tures. Distribute at least 3 alarms on 15 m of
corridor. Attach alarms in the middle of cor-
ners and crossroads in the corridor.
Halls and corridors
:
≤
15 m
≤
7,5 m
≤
7,
5 m
x
0,50 m < x < 1 m
x
< 1 m
0,50 m < x < 1 m
≥
1 m
A + B
: For pointed and flat gables with a ceiling area of less than 1 m width: Attach
alarms at a minimum distance of 0.50 m and a maximum distance of 1 m to the top.
C
: For flat gables with a ceiling area of more than 1 m width: Attach to the middle of
the ceiling like in other rooms.
A
B
C
Gables
: