34
Setting the parameters for all models
Smoke alarm Salva KNX
• Version: 09.09.2016 • Technical Changes and Errors excepted.
If the button acknowledgement is to be sent to the bus, set the function to "yes". Ac-
knowledgement is automatically switched off again 10 minutes after the end of the
smoke detection.
Then determine the value for the output object "smoke alarm: button acknowledge-
ment" in case of active acknowledgement and when it is to be sent.
External alarm
If an alarm message from another device to this device is also to trigger an alarm, then
set the function to "yes". Then determine the value for the alarm input object "smoke
alarm: external alarm" at which the external alarm should be active.
Sensor malfunction
If a sensor malfunction is to be sent to the bus, set the function to "yes".
Then determine the value for the output object "smoke alarm: malfunction" in the event
of a malfunction and when it is to be sent.
Battery warning
If a warning is to be issued when the battery is nearly flat, set the function to "yes".
A battery that is nearly flat is also always indicated locally on the device.
Use button acknowledgement
No • Yes
Object evaluation
1 = active • 0 = active
Send pattern
• on change
• on change to active
• on change to inactive
• on change and periodically
• on change to active and periodically
• on change to inactive and periodical
Cycle
(if sent periodically)
5 s • 10 s • 30 s • ... 2 h
Use external alarm
No • Yes
Object evaluation
1 = active • 0 = active
Use malfunction object
No • Yes
Object evaluation
1 = active • 0 = active
Send pattern
• on change
• on change to active
• on change to inactive
• on change and periodically
• on change to active and periodically
• on change to inactive and periodical
Cycle
(if sent periodically)
5 s • 10 s • 30 s • ... 2 h
Use battery warning
No • Yes
Summary of Contents for Salva KNX basic