MP500/4N-8-16 Installation
95
6 - COMMISSIONING
This chapter contains explanations for all the operations to be carried out for the commissioning of the alarm system, after having
fastened all the devices and made all the connections.
Once the operations described in this chapter have been concluded, the system can then be programmed according to the instructions
found in the
Programming Manual
.
6.1
SYSTEM POWER SUPPLY
Before powering up the system, it is necessary to check that the connections are all correct. Therefore, power up the system according
to the sequence below.
1. If there are supplementary power supply units, power them up before connecting the control panel.
2. Insert the battery in the dedicated compartment of the control panel and connect the Faston connectors to the relative terminals: red
“
+
”, black “–“, and then turn on mains power supply. The rated voltage to the battery terminals once charged reaches 13.8 V. The
power supply does not need calibration.
IMPORTANT!
The control panel has a battery control circuit. If the battery is not connected to the terminals of the
connection cables, (red and black Faston) there is no power.
3. On the control panel, the POWER LED is on (indicating the presence of current). After a few seconds, when the start-up routine has
been completed and the control panel is fully operative, the RUN LED begins to flash slowly (approximately one flash every 2
seconds).
4. In the other devices, when they are powered, the yellow LED next to the programming button will flash for 10 seconds (the buzzer in
the keypad will also sound). After 10 seconds have passed, this LED begins to flash slowly (approximately once every 2 seconds) until
the device is not acquired, and will then shut off. For the acquisition procedure, see paragraph
If the device results already acquired and configured, the LED turns off after 10 seconds.
5. Check that voltages arriving to the devices in the various points of the system are in conformity with the indications described in
Sizing of the power supply cable
IMPORTANT!
To turn off the system completely, follow the procedure indicated in paragraph
6.1.1 RUN LED Indications
The RUN LEDs provide the following information.
Warning
LED
Description
Meaning
When
Normal
operation
Blink every 2 seconds
Control panel without
peripheral devices
registered
The blinking continues until the first
keypad is acquired
Slow blinking
Microprocessor in run and
nothing else to signal
Always present when the control panel
functions normally
Fault
Fast blinking
No battery or connection
cables inverted
The blinking continues until the battery is
connected or the right cables are
inserted
Steady on with brief
interruption every 2
seconds
Irreversible failure
6.2
ACQUISITION OF BUS DEVICES
6.2.1 Position of the programming buttons
For the acquisition of the bus devices, use their programming buttons (PROG).
The images below demonstrate where these buttons are positioned.
Figure 63 - Position of the programming buttons
AS500/RPT EXPANSION
KEYPAD
EXPANSION
READER
RADIO EXPANSION