Please pay particular attention when wiring CANopen
®
connection: at both ends
there must be a
120Ω
resistor and the bus length must be the following:
B
IT RATE
B
US LENGTH
1 Mbit/s
25 m
500 Kbit/s
100 m
250 Kbit/s
250 m
125 Kbit/s
100 m
DEVICE 1
DEVICE 2
DEVICE 127
120 Ohm
120 Ohm
2.3.5
RS232 Mode
The RS232 Mode allows you to drive your motor via Telemetry Panel (See Chapter
4) or send the control commands
to the UNIDRIVE through the RS232 protocol.
This operating mode can be useful for testing your motor, without worrying about
other devices (e.g: potentiometer) or other controllers (e.g: PLC) (See Section
4.2.4). See Figure 2.12 for wiring diagrams for this operating mode and Table 2.9
for a description of inputs and outputs.
Table 2.9:
UNIDRIVE I/O definitions for
RS232
Mode.
P
IN
I/O
T
YPE
N
AME
D
ESCRIPTION
26
IN6
EMERGENCY
Emergency input should always be
supplied, otherwise UNIDRIVE stops
motor rotation and unlocks motor brake.
Mandatory
29
OUT4
ALARM
Alarm output, it changes its current state
whenever an alarm is present. See Section
2
For further information, see
UNIDRIVE - RS232 Communication Protocol
document
30
Chapter 2
Installation and Wiring