Diagnostics
5
© ELETTROQUADRI S.r.l.
45 / 66
INSTALLATION MANUAL
Er - 45
Incompatibility error between the various boards in car serial transmissions
Not
recoverable
•
Call ELETTROQUADRI S.r.l.
Er - 46
Incompatibility error between the various boards in floor serial transmissions
Not
recoverable
•
Call ELETTROQUADRI S.r.l.
Er - 47
Call button blocked
Recoverable
Hold down the PROGR key on REMP2, the display will show:
•
PC for car buttons.
•
PP for floor buttons, alternating with the number of the floor in error.
The floor number is absolute, i.e. 0 is the lowest floor.
If more than one floor button is blocked, the highest one is displayed each time.
Verify:
•
Disconnect the connector for the reported call on the FLSER board.
Er - 65
Position and speed of car via the MP-ENC board
Not
recoverable
•
Call ELETTROQUADRI S.r.l.
Er - 66
Position and speed of car via the MP-ENC board = not active
Not
recoverable
•
Call ELETTROQUADRI S.r.l.
Er - 67
Regulation EN 81-20/EN 81-50 - When the car side A door opens, monitor the opening of the
car side A auxiliary contact
Recoverable
The MPCAB board verifies the lack of input J21/3 (CF1).
Verify:
•
Operation of the car side A auxiliary contact.
Er - 68
Regulation EN 81-20/EN 81-50 - When the car side A door opens, monitor the closure of the
car side A auxiliary contact
Recoverable
The MPCAB board verifies the presence of input J21/3 (CF1).
Verify:
•
Operation of the car side A auxiliary contact.
Er - 69
Regulation EN 81-20/EN 81-50 - When the car side B door opens, monitor the opening of the
car side B auxiliary contact
Recoverable
The MPCAB board verifies the lack of input J21/4 (CF2).
Verify:
•
Operation of the car side B auxiliary contact.
Er - 70
Regulation EN 81-20/EN 81-50 - When the car side B door opens, monitor the closure of the
car side B auxiliary contact
Recoverable
The MPCAB board verifies the presence of input J21/4 (CF2).
Verify:
•
Operation of the car side B auxiliary contact.
ELETTROQUADRI
SINCE 1983
MP3