Programming
4
© ELETTROQUADRI S.r.l.
27 / 66
INSTALLATION MANUAL
ENT/RST
Pt
Timer programming
Code
range
unit
of
measurement
default meaning and use
t0
20 to 90
sec
20
high speed travel in normal operation timeout
t1
2 to 60
sec
8
floor time
t2
0 to 30
dsec
0
door open delay after retiring cam drops
t3
1 to 90
sec
60
return to main delay
t4
1 to 90
min
15
return to lowest floor
t5
8 to 60
sec
15
door timeout
t6
0 to 30
dsec
0
door open control signal drop delay
t7
0 to 30
dsec
15
door closure control signal drop delay in parking
t8
20 to 90
dsec
40
occupied after parking
t9
0 to 99
dsec
0
star/delta switching
tA
0 to 99
dsec
0
motor disconnect delay
tb
4 to 250
dsec
4
wait for DRA
tC
20 to 250 sec
100
emergency car intervention delay
td
5 to 99
sec
15
send to parking delay
tE
50 to 250 sec
0
CPV activation delay
tF
0 to 250
sec
0
wait at main floor before starting
tH
0 to 50
dsec
0
delay for retiring cam to rise
tL
0 to 99
sec
70
movement impeded or doors indication delay
tn
3 to 30
sec
20
low speed travel in normal operation timeout
to
0 to 25
dm/sec
0
car speed (not a timer).
tP
10 to 99
dsec
25
FS drop delay
tr
0 to 10
dsec
0
stop in up travel delay
tt
0 to 10
dsec
0
stop in down travel delay
tU
0 to 99
num
20
forgotten call calculation kappa (not a timer)
P0
2 to 50
dsec
3
delay on stop (fire services only)
P1
0 to 120
sec
0
startup latency (Ziel-Habegg)
P2
0 to 50
dsec
0
preliminary closure latency
P3
3 to 250
sec
20
car light duration
P4
0 to 99
dsec
0
retiring cam deactivation delay after doors closed
P5
5 to 60
dsec
30
FS rise delay
P6
0 to 80
dsec
20
on-the-fly reset latency
P7
0 to 250
sec
0
valve test duration (0 = disabled)
P8
0 to 80
dsec
0
second valve opening advance.
NGV version: both signals lacking latency
P9
0 to 80
dsec
0
second valve closure delay.
NGV version: stop timeout, after UP drops
PA
0 to 50
dsec
0
up releveling disconnect delay
Pb
0 to 50
dsec
0
down releveling disconnect delay