RADIO TRANSMITTER

DIP4 - OFF =>

It cyclically commands open-stop-close-stop-open-etc.

DIP4 - ON =>

It opens the gate when this is closed. If It Is operated

while the gate Is opening, It has no effect. If It Is

operated when the gate Is open, It closes. If It Is

operated while the gate Is closing, It opens the gate

again.

AUTOMATIC CLOSING

Pause times before the automatic closing of the gate are set with the

timing procedure.

The maximum pause time Is 5 minutes.

Pause time can be started or stopped by DIP3 (ON started).

Pedestrian pause time can be started or stopped by DIP9 (ON started).

ELECTRIC LOCK 

Set Dip11 to ON to enable control of the electric lock in the opening

phase. 

RELEASE PULSE IN OPENING PHASE 

Set Dip10 to ON to enable the release pulse of the electric lock in the

opening phase (provided  Dip11 is set to ON) 

With the gate closed, pressing an opening command will cause the gate

to perform the closing movement for 0.5s (in this phase the Encoder(s)

is/are not enabled), and simultaneously the electric lock is activated

(followed by 0.5s pause and then by opening of the gate).

GATE LEAF RELEASE ASSIST: 

With the electric lock release pulse active (Dip10 - ON), when the gate

is closed a direction reversal manoeuvre is performed for a fixed time

of 0.2s to facilitate manual release (in this phase the Encoder is not

enabled).

OPERATION AFTER BLACK-OUT

When mains electrical power is restored press the opening button (K,

OPEN, radio).

The gate will open. Let the gate close itself with automatic closure or

wait that the flasher stops blink first to command the closing movement.

This operation is valid to obtain the leaves position readjustment.

During this phase all safety devices are active.

INTRUSION ALARM MODE (ABIS System)

ABIS facility (Anti Break-in System) is available only in operator

PRINCE 24V PLUS (DIP 12 ON position) with encoder proper

connected (DIP 7 ON or OFF position).

Operation: only with gate completely closed, in case of manual forcing

of the shutters, the motor/s are selected to close, preventing access. In

the meantime the output to SIREN is enabled, and remains activated for

7 sec .

In case the intrusion prevention mode is enabled, all commands are

inhibited, hence the gate can be selected open only after 7 sec.

Should the motor work without ABIS facility, it is advisable to instal an

electrical lock to ensure an efficient locking of the gate.

SIREN (- 

+)

Current supplied for siren operation (300 mA max, 12Vdc)

It is possible to install a siren (code ACG2278) to monitor the manual

forcing of the gate and thus the intrusion of unauthorized persons.

Siren facility is available only in operator PRINCE 24V PLUS (DIP 12

ON position) with encoder proper connected (DIP 7 ON or OFF

position).

S

AFETY ACCESSORIES OPERATION

ENCODER

It serves as a safety device both during opening and on closure,

with movement reversion. DIP 7 (ON) OPERATES THE MOTOR

WITH ENCODER.

If You move DIP 7 OFF, You have also to move jumpers JP1 and

JP2 in up position (refer to previous page point C).

If the Encoder does not work (due to a failure In the power supply,

disconnected wires, broken or defective disk), the gate Is not operated.

If the encoder operates the closing or the opening and than gives a

reverse command, the gate stops and reverses Its movement for 1

second. 

If linked, the buzzer buzzes to alarm for 5 minutes and the

blinker blinks for 1 minute. 

During or after the 5 minutes, when the buzzer alarms, you can make

the gate work again just pressing the operating button you want.

PHOTOCELL 1 (COM-PHOT 1)

If DIP 6 is OFF => 

The gate does not open if there is an obstacle within

the photocells range of action. During operation,

photocells work both when the gate opens (by

starting the opening movement again after half a

second time), and when it closes (by starting the

reverse movement after one second time).

If DIP 6 is ON =>

If there is an obstacle within the photocells range of

action when the gate is closed and its opening is

commanded, the gate opens (during Its opening,

photocells do not work). Photocells work only while

the gate Is closing (by starting Its reverse motion

after one second, even if they are still engaged).

STOP BUTTON

The STOP button stops the gate during any operation. 

If you push it when the gate is totally open (or partly open, by using the

pedestrian command), this button temporary excludes the automatic

closing (if selected by DIP3 or DIP9). It Is than necessary to operate

another command to make the gate close again.

The automatic closing function Is enabled again with the following

operating cycle (if selected by DIP3 or DIP9).

BLINKER

N.B.: This electric board can supply power ONLY TO BLINKERS

WITH BLINKING CIRCUIT.

Use flasher (ACG7061) with lamp 24V 20W max.

PRE-BLINKING FUNCTION:

DIP 8  - OFF =>

the motor, the blinker and the buzzer start at the same

time.

DIP 8 - ON =>

the blinker and the buzzer start 3 seconds before the

motor.

BUZZER (Optional)

Current as supplied for buzzer operation 200 mA 12Vdc

The buzzer emits an intermittent sound signal during opening and

closing cycles. When safety devices are operated (alarm), the

intermittence frequency of this sound signal Increases.

WARNING LIGHT - GATE OPEN  (COM-SIGNAL):

Its function Is to signal when the gate Is open, partly open or not totally

Dip position for PRINCE with Encoder

DIP 7 ON - Current sensors Off / Encoder On

Dip position for PRINCE with Current sensors

DIP 7 OFF - Current sensors On / Encoder Off

GG

BB

Summary of Contents for KIT PRINCE PLUS 24V

Page 1: ...PLUS 24V 230V 50 60Hz AD00730 Peso max cancello Poids maxi portail Max gate weight Max Torgewicht Peso m x verja 200Kg 550lbs Spinta Pouss e Thrust Schubkraft Empuje 100Kg 275lbs Spinta max Pouss e ma...

Page 2: ...RVER SOIGNEUSEMENT CES INSTRUCTIONS 1 Si la centrale lectrique ne dispose d aucun interrupteur il faut en installer un de type magn tothermique en amont de cette derni re omnipolaire avec ouverture mi...

Page 3: ...HE SAFETY OF THE PEOPLE IT IS IMPORTANT TO FOLLOW ALL THE INSTRUCTIONS INSTALLATIONSVORSCHRIFTEN BEACHTET WERDEN 1 Wenn nicht bereits an der elektrischen Schaltzentrale vorgesehen muss vor der Schaltz...

Page 4: ...sistema respetando las normas y las leyes vigentes SEGUIR TODAS LAS INSTRUCCIONES DE INSTALACI N 1 Este manual de instrucciones est exclusivamente dirigido a personal especializado que conozca los cr...

Page 5: ...BIS utile nel caso manchi l elettroserratura CARATTERISTICHE TECNICHE Lunghezza max anta Peso max cancello Corsa max di traino Tempo medio di apertura Velocit media di traino Alimentazione Potenza nom...

Page 6: ...li posti su siti privati ed i 390N per i cancelli posti su siti commerciali ed industriali valori indicati nel punto 5 3 5 della norma EN 12453 FISSAGGIO ATTACCO MOTORE A COLONNA Installando il PRINCE...

Page 7: ...2 X A 20 100 100 765 90 13 5 S2 Y A 40 100 100 765 90 13 5 S3 X A 60 110 100 765 90 14 S3 Y A 80 140 110 765 115 17 S3 X B 100 160 110 765 115 18 S3 X B 120 180 110 765 115 19 5 S3 X B 140 210 110 765...

Page 8: ...rlo serrando la vite da 8mA con una chiave fissa n 13 Per ottenere la chiusura desiderata si dovr spostare il fermo B OPZIONALE bloccandolo come descritto per il fermo A MANUTENZIONE Da effettuare sol...

Page 9: ...ZIONE ALLE POLARIT Collegamento led stato batteria 12Vdc Spia cancello aperto 12Vdc 3W max Collegamento sirena anti intrusione 12Vdc max 300mA Collegamento segnalatore sonoro 12Vdc max 200 mA Collegam...

Page 10: ...IP 8 Prelampeggio ON Lampeggio normale OFF DIP 9 Tempo di attesa prima della chiusura automatica pedonale ON DIP 10 Abilitazione colpo di sgancio serratura elettrica ON attivata DIP 11 Abilitazione se...

Page 11: ...oni stop allarmi ecc 8 La chiusura delle ante verr eseguita in modalit veloce e in prossimit della totale chiusura in modalit rallentata 9 Finito il conteggio dell ENCODER il cancello si ferma A FINE...

Page 12: ...c possibile comandare il cancello in apertura Nel caso tale funzione non venga abilitata e si utilizzi il sensore di corrente si consiglia l opzione di una elettroserratura per una efficace chiusura S...

Page 13: ...a 50 60 Hz Alimentazione batterie 20 24 5Vdc Peso senza batteria kg 3 0 Grado di protezione del contenitore a parete IP55 Ingombro contenitore a parete 33x24 2x12 4 Potenza Trasformatore 130VA V prima...

Page 14: ...o batteria Al ritorno della tensione di rete si consiglia di far aprire completamente il cancello Lasciate che il cancello si chiuda da solo con la chiusura automatica o attendete che il lampeggiatore...

Page 15: ...ux CARACTERISTIQUES TECHNIQUES Longueur maxi du battant Poids maxi du battant Course maxi d entrainement Temps moyen d ouverture Vitesse de traction Alimentation Puissance moteur vis a 71 rpm Puissanc...

Page 16: ...ontact raccord aux bornes adapt es de la platine lectronique la mise en marche de l automatisme si le portillon est ouvert Ne pas g n rer de zone d crasement par exemple entre le vantail ouvert et la...

Page 17: ...S2 X A 20 100 100 765 90 13 5 S2 Y A 40 100 100 765 90 13 5 S3 X A 60 110 100 765 90 14 S3 Y A 80 140 110 765 115 17 S3 X B 100 160 110 765 115 18 S3 X B 120 180 110 765 115 19 5 S3 X B 140 210 110 76...

Page 18: ...placer le collier A et de le bloquer en vissant la vis M8 avec une cl n 13 Pour obtenir la fermeture desir e il est necessarie de deplacer le collier B OPTIONAL et de le bloquer comme indiqu ci dessu...

Page 19: ...12Vdc Voyant portail ouvert 12Vdc 3W max Branchement sir ne anti intrusion 12Vdc max 300mA Branchementavertisseursonore 12Vdcmax200mA Branchement serrure lectrique MAX 15W 12V Connecteur pour carte d...

Page 20: ...OFF DIP 9 Temps d attente avant la fermeture automatique pi tonne ON activ e DIP10 Habilitation coup de d clenchement serrure lectrique ON activ e DIP11 Habilitation serrure lectrique ON activ e DIP12...

Page 21: ...pr c dant la fermeture automatique max 5 minutes 6 Appuyer sur la touche PROG Arr t du comptage du temps d attente pr c dant la fermeture automatique M2 ferme D part du comptage du retard 7 Appuyer su...

Page 22: ...cette op ration ne sont pas habilit s Simultan ment la serrure lectrique est activ e suivie de 0 5s de pause et de l ouverture du portail FACILITES DE DEBLOCAGE BATTANTS Avec le d crochage de la serr...

Page 23: ...t et le buzzer d marrent 3 secondes avant le moteur BUZZER Option Courant fourni pour le fonctionnement du buzzer 200 mA 12Vdc Pendant l ouverture et la fermeture le buzzer mettra un signal sonore int...

Page 24: ...V apr s quoi une signalisation donn e par la fiche de recharge la centrale interviendra qui bloquera le portail et fera clignoter le voyant d tat batterie Au retour du courant nous conseillons de fair...

Page 25: ...o break in and keep the gate closed by running the motor TECHNICAL DATA Max leaf length Max leaf weight Max travel Average opening time Operating speed Power supply Nominal Motor capacity Max Motor ca...

Page 26: ...riate steps in accordance with EN 12453 norm for instance by preventing the operation of the motor when the pedestrian opening is opened by installing a safety microswitch connected with the control p...

Page 27: ...A 20 100 100 765 90 13 5 S2 Y A 40 100 100 765 90 13 5 S3 X A 60 110 100 765 90 14 S3 Y A 80 140 110 765 115 17 S3 X B 100 160 110 765 115 18 S3 X B 120 180 110 765 115 19 5 S3 X B 140 210 110 765 115...

Page 28: ...e needed position by tightening the 8mA screw with a n 13 key To obtain the desired closing limit you must adjust the stopper B OPTIONAL in the needed position and tighten it as for stopper A MAINTENA...

Page 29: ...flasher 24Vdc code ACG7061 FOLLOW THE POLARITY Wiring battery status led 12Vdc Lamp gate open 12Vdc 3W max Wiring intrusion alarm siren 12Vdc max 300mA Wiring acoustic warning 12Vdc max 200 mA Electri...

Page 30: ...lock to ensure an efficient locking of the gate DIP 8 Pre blinking ON Normal blinking OFF DIP 9 Pause time before the automatic pedestrian closing ON DIP 10 Enable unlock stroke of electric lock ON ac...

Page 31: ...measurement the gate stops AFTER PROGRAMMING SWITCH DIP 2 TO OFF MODE 2 1 Start with the gate completely closed 2 Switch DIP 2 to ON LED DL7 will blink rapidly 3 Press PROG M1 opens 4 When the gate co...

Page 32: ...ilable only in operator PRINCE 24V PLUS DIP 12 ON position with encoder proper connected DIP 7 ON or OFF position SAFETY ACCESSORIES OPERATION ENCODER It serves as a safety device both during opening...

Page 33: ...ains drops 100ms Max capacity of the warning light gate open 12Vdc 3 W corresponding to 1 3W lamp or to 5 LEDS with 2 2 k resistance In series Max load flasher 24Vdc 20W All the inputs must be used as...

Page 34: ...re is a power cut the functioning of the gate is guaranteed up to a charging level of approximately 20V following which a signal is sent by the recharge card to the control unit which blocks the gate...

Page 35: ...von au en ge ffnet wird siehe Abs ABIS System TECHNISCHE EIGENSCHAFTEN Max Torfl gelweite Max Torgewicht Max Hub Mittlere ffnungszeit zirka Laufgeschwindigkeit Stromspannung Motorleistung Max Motorle...

Page 36: ...g setzen des Motors per Handsender wenn der Gehfluegel geoeffnet ist Das zu vehindern koennen sie einen Endschalter anschliessen der beim oeffnen des Gehfluegel andere automatischen funktionen ausser...

Page 37: ...A 20 100 100 765 90 13 5 S2 Y A 40 100 100 765 90 13 5 S3 X A 60 110 100 765 90 14 S3 Y A 80 140 110 765 115 17 S3 X B 100 160 110 765 115 18 S3 X B 120 180 110 765 115 19 5 S3 X B 140 210 110 765 115...

Page 38: ...nungsweite einzustellen gen ngt es die Endschalter A zu verstellen und sie mit Hilfe eines Imbusschl els an der Mutterschraube festzuziehen Um die erw nschte Schliessweite einzustellen m ssen Sie die...

Page 39: ...4Vdc cod ACG7061 Achtung auf die Polen Led Anschluss an Batterie 12Vdc Anzeiger f r Tor offen 12Vdc 3W max Sirenen Anschluss mit Eindringungsschutz 12Vdc max 300mA Verbindung zu Ton Signal 12Vdc max 2...

Page 40: ...s Schloss zur sicheren Verrieglung einbauen DIP 8 Vorblinken ON Normales Blinken OFF DIP 9 Wartezeit vor dem automatischen Schlie en der Personen ffnung ON DIP 10 Zulassung Arrestgriff Elektroschloss...

Page 41: ...inken und meldet so den Ausgang aus der Lernprozedur Von diesem Zeitpunkt an funktionieren die Sicherungen und andere Steuerungen des Tores automatisch Umkehrungen Stop Alarme usw 8 Das Schlie en der...

Page 42: ...chliessen oder warten Sie da die Blitzgeberanschl ge zuerst blinken um die schlie ende Bewegung zu beherrschen Dieser Betrieb ist g ltig zu erreichen l t Position Nachjustierung W hrend dieser Phase s...

Page 43: ...ustisches Wechselsignal Falls Sicherheitsvorrichtungen Alarme ausgel st sind wird die Frequenz der Signalschwankung erh ht KONTROLLEUCHTE TOR OFFEN COM SIGNAL Besitzt die Aufgabe ein offenes auch wenn...

Page 44: ...trale angeschlossen werden wird bei Stromausfall die Tor Funktionierung bis zu einem Ladeniveau von zirka 20V garantiert dar ber hinaus wird eine Signalisierung der Aufladung durch die Karte an die Ze...

Page 45: ...S til en los casos donde NO se utiliza la electro cerradura CARACTER STICAS T CNICAS Longitud m xima de la anta Peso m x cancela Corrido max de arrastre Tiempo de abertura Velocidad de arrastre Alimen...

Page 46: ...a EN12453 por ejemplo impedir el movimiento del motor cuando la puertecilla est abierta gracias a un microinterruptor debidamente conectado a la central No hay que generar puntos donde se pueda quedar...

Page 47: ...90 13 5 S2 X A 20 100 100 765 90 13 5 S2 Y A 40 100 100 765 90 13 5 S3 X A 60 110 100 765 90 14 S3 Y A 80 140 110 765 115 17 S3 X B 100 160 110 765 115 18 S3 X B 120 180 110 765 115 19 5 S3 X B 140 21...

Page 48: ...vite da 8mA con la llave fija n 13 Para obtener el cierre deseado se tendr que mover el seguro B OPCIONAL bloccandolo come descritto per il fermo A MANTENIMIENTO Estas operaciones deben ser efectuada...

Page 49: ...dc Intermitente de 24Vdc c d ACG7061 ATTENCI N A LA POLARIDAD Conexi n led a bater a 12Vdc Indicador verja abierta 12Vdc 3W max Conexi n sirena contra intrusiones 12Vdc max 300mA Indicador ac stico 12...

Page 50: ...cerradura en la hoja DIP 8 Pre destello ON Destello normal OFF DIP 9 Tiempo de la pausa antes de cerrar peatonal autom tico ON DIP 10 Abilitaci n golpe de desbloqueo cierre el ctrico ON activada DIP 1...

Page 51: ...ne del procedimiento de memorizaci n Desde este momento las protecciones y otros mandos de la cancela funcionan normalmente inversiones paradas alarmas etc 8 El cierre de las puertas se efectuar en mo...

Page 52: ...ones est n activadas FUNCI N ANTI INTRUSI N ABIS System La funci n ABIS Anti Break in System est habilitada s lo y exclusivamente con motores PRINCE 24V PLUS DIP 12 en ON con encoders conectados DIP 7...

Page 53: ...se alar que la verja est abierta parcialmente abierta o en todo caso no totalmente cerrado Se apaga solamente cuando la verja est cerrada del todo Durante la programaci n esta se al no est activada N...

Page 54: ...ectan bater as a la central en ausencia de tensi n de red el funcionamiento de la cancela se garantiza hasta un nivel de carga de 20V luego de lo cual subentra una se al dada de la tarjeta de recarga...

Page 55: ...d autres l ments Aussi rentre t il dans le champ d application de l art 6 paragraphe 2 de la Directive machines 2006 42 CEE et de ses modifications successives Sa mise en service est interdite avant q...

Page 56: ...ella Perno ANGOLARE ATTACCO A COLONNA 2 pezzi Mors Mammut5P OK431 NYLP per PRINCE 24V PLUS BLOCCA CAVO PRINCE SR6P 4 per PRINCE 24V PLUS Chiocciola bronzo FORCELLA POSTERIORE Boccola vite senza fine V...

Reviews: