WARNING!
The length of connection cables from the motors to the control panel unit must not exceed 15 m. The wire section of the motor power supply must be
1.5 mm
2
, whilst that of the accessories must be 0,75 mm
2
. As for the encorder it is very important to use a shielded wire with a section of 0,75 mm
2
(for example type ÖLFLEX-110 CH - Cod.ACG2133). It is compulsory to use shielded cable for the encoder in order to guarantee the correct operation
of the control board.
The shield of the ENCODER cable must be earth grounded at one end (not to the card GND), and at the opposite end the
shield must be free (conductor not connected).
To ensure the correct functioning of the installation it is advisable to wire encoder and motor with separate cables.
Dip position for
PRINCE with
Encoder
Dip position for
PRINCE with Current
sensors
DIP 7 ON - Current sensors Off / Encoder On
DIP 7 OFF - Current sensors On / Encoder Off
Electric board KS2 24V cod. BC07049
Radio antenna
Common contact unit
Photocell contact (NC)
Stop button contact (NC)
Opening button contact (NO)
Closing button contact (NO)
Single pulse contact (NO)
Positive for accesories supply: 24Vdc
Negative for accessories supply: 24Vdc
Wiring of flasher 24Vdc
(code ACG7061)
(
FOLLOW THE POLARITY
)
Wiring battery status led (12Vdc)
Lamp gate open (12Vdc 3W max)
Wiring intrusion alarm siren (12Vdc max 300mA)
Wiring acoustic warning (12Vdc max 200 mA)
Electric lock connection (Max 15W 12V)
Connector for battery charge card, 24Vdc (code
ACG4648)
Connector for EXPANDER card (code
ACG5471)
Connector for radio receiver, supply 24Vdc
J1
J2
J3
J4
AERIAL
COM
PHOT.1 NC
STOP
OPEN
CLOSE
K BUTT.
A+D+
A-D-
SIGNAL BATTERY
SIGNAL
SIREN
BUZZER
LOCK
BATTERYCHARGER
EXP. 12V
RADIO
Wiring MOTOR 1 (no polarity)
Wiring MOTOR 2 (no polarity)
Connector for transformer secondary
Connection block for wiring of ENCODER M1and M2
Signal ENCODER M1
Positive supply ENCODER M1
Negative supply ENCODER M1 and M2
Positive supply ENCODER M2
Signal ENCODER M2
Connector for factory encoding.
Do not alter the
position of the jumper located as shown in
figure
Verify that the jumper is inserted !
Supply 230 Vac 50/60Hz (external to the card)
(on request 120V/60Hz)
Electronic regulator for low speed
Selection of motor type for operation with current
sensor M1
Selection of motor type for operation with current
sensor M2
Selection of operation with 1 or 2 motors (default
closed loop 2 motors)
Current sensor regulator for motor 1
Current sensor regulator for motor 2
J5
J6
J7
J8
JP5
J9
LS
JP1
JP2
JP3
M1
M2
MOTOR 1
MOTOR 2
SEC.TRANSF.
ENCODER
S-M1
+ M1
GND
+ M2
S-M2
SW
L1 - N
LOW SPEED
GG
BB