-21-
Section 8 - Operating instructions
ACCESS LEVELS
SWITCH ON/REBOOT SCREEN
The European standard EN54-2 requires access to the control equipment to be split in to 4 levels. The control
unit complies through the use of passwords. In order to meet these requirements the control unit door should
not be locked.
The ED700A and ED816A systems use the following method of access control:
No password required, allowing access by the general public, or persons having a general responsibility for
safety supervision, who might be expected to investigate and initially respond to an alarm or fault warning.
System password is factory set as “AAAAAA”, allowing access by persons having a specific responsibility for
safety, and who are trained and authorized to operate the control unit in the following conditions:
1.
Quiescent condition;
2.
Alarm condition;
3.
Fault condition;
4.
Disabled/isolated condition;
5.
Test condition.
System password is factory set as “BBBBBB”, allowing access by persons who are trained and authorized to:
1.
Re-configure the site specific data held within the control unit and equipment connected to it.
2.
Maintain the system.
Connection to PC and the use of Fireconfig software is required, allowing access by persons trained to re-
configure the system.
At switch on or after system reboot the following screen will be displayed:
Each loop card fitted should be listed as responding. Each display / repeater has a different ID, set via dip
switches. No two repeaters should have the same ID.
Press the menu key and the following screen will be displayed:
This is the normally displayed screen. The text in the top right can, at commissioning, be changed to suit each
application.
Access level 1
Access level 2
Access level 3
Access level 4
ED720 SYSTEM CHECKING FOR LOOP CARDS:
1. RESPONDING
5.
2. RESPONDING
6.
3.
7.
4.
8.
THIS DISPLAY ID: RACK 0
10:51 05/06/08
ELECTRONIC DEVICES
NO OF DETECTORS IN ALARM:
0
IN
0 ZONES
PRE ALARMS
0 FAULTS
0
ISOL ZONES
0
ED816A Addressable Fire and gas detection Installation manual 8-9-08 Rev-a