CONTROL SYSTEM
11-2
Revision 0
Service Manual – WNG DCI
Target frequency limits as a function of outdoor air temperature )OAT(:
OAT Range
Cool mode limits
Heat mode limits
OAT
No limit
< 6
6 ≤ OAT < 15
MaxFreqAsOAT1H
15 ≤ OAT < 24
MaxFreqAsOATC
24 ≤ OAT
No limit
MaxFreqAsOAT2H
11.1.4
Frequency Changes Control
Frequency change rate is 1 Hz/sec.
11.1.5
Compressor Starting Control
Frequency
Time
Min 10 Minutes
1
Minute
Step 1
Step 3
1
Minute
Step 2
11.1.6
Minimum On and Off Time
3 minutes.
11.1.7
Indoor Fan Control
10 Indoor fan speeds are determined for each model. 5 speeds for cool/dry/fan modes and 5
speeds for heat mode.
When user sets the indoor fan speed to a fixed speed )Low/ Medium/ High(, unit will operate
constantly at set speed.
When Auto Fan is selected, indoor unit controller can operate in all speeds. The actual speed is set
according to the cool/heat load.
11.1.7.1
Turbo Speed
The Turbo speed is activated during the first 30 minutes of unit operation when auto fan speed is
selected and under the following conditions:
Difference between set point and actual room temperature is bigger then 3 degrees.
Room temperature
22 for cooling, or
25 for heating.
>
<
5HYLVLRQ<
Summary of Contents for ONG 25 DCI INV
Page 59: ...AUTO...
Page 60: ......
Page 68: ......
Page 69: ......
Page 70: ...1 AUTO...
Page 71: ...2 9 10 11 12 13 14 15 AUTO 1 2 3 4 5 6 7 8 16 17 18...
Page 72: ...3...
Page 73: ...4...
Page 74: ...5 COOL ESF EN RESET HEAT MODE F A PWR ESP PWR...
Page 75: ...6...
Page 76: ...7 AUTO AUTO...
Page 77: ...8...
Page 78: ...9...
Page 79: ...10...
Page 80: ...11...