PERFORMANCE DATA
5-2
Revision 0
Service Manual – WNG DCI
5.1.3
Heating Capacity (kW) - Run Mode
ID COIL ENTERING AIR DB TEMPERATURE [ºC]
OD COIL
ENTERING AIR
DB/WB
TEMPERATURE
[ºC]
DATA
15 20 25
TC
2.16 2.01 1.86
-15/-16
PI
0.49 0.54 0.58
TC
2.41 2.26 2.11
-10/-12
PI
0.59 0.64 0.68
TC
2.59 2.44 2.29
-7/-8
PI
0.66 0.71 0.76
TC
2.68 2.53 2.38
-1/-2
PI
0.70 0.75 0.80
TC
2.75 2.59 2.44
2/1
PI
0.72 0.77 0.82
TC 3.55
3.40
3.25
7/6
PI 0.76
0.81
0.86
TC
3.75 3.60 3.44
10/9
PI
0.81 0.86 0.90
TC
3.94 3.79 3.64
15/12
PI
0.85 0.90 0.95
15-24
TC
85 - 105 % of nominal
(Protection Range)
PI
80 - 120 % of nominal
LEGEND
TH – Total Heating Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OU - Outdoor
5.1.4 Capacity
Correction
Factors
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
-15
-10
-5
0
5
10
15
Outdoor WB Temperature [deg C]
Ca
p
a
c
it
y
Ra
ti
o
5HYLVLRQ<