background image

No heat pump

There is no connection to the outdoor unit module. Check the power supply and
the interface cable to the outdoor unit module 

Frozen boiler

When   the   power   supply   is   turned   on,   the   water   in   the   water   heater   has   a
negative temperature and may have frozen. Check the integrity of the water tank
and then turn it on again 

Unprotected

solar

The solar installation is switched off from the menu "

Heat sources

" and if it

exists, it may be damaged by overheating or freezing

Heat sources

turned off 

All   heat   sources   in   the   menu   "

Heat   sources

"   are   turned   off.   If   the   solar

installation   exists,   it  may   be  damaged  by  overheating  or  freezing.   The   same
applies to switching off the mode for protection of the water tank against freezing.

Overheating

solar 

Overheating of the solar system is registered, if the temperature t3 exceeds the
temperature in the field "

Overheating solar

" in the menu "

Solar protection

"

Overheating

boiler

The temperature at the top of the water heater exceeded 84 ° C

Anti-

Legionella

The Legionella bacteria destruction mode was activated by heating the water by
the electric heater up to 70 ° C 

Power supply

off 

Last time and date when the thermoregulator was running before power supply
was interrupted 

Power supply

on 

Time and date, when the power supply was restored.

The above two messages will be registered if the system clock is set 

Damaged

Flash

A malfunction of the microcontroller resulting in the failure to record the settings
in the non-volatile memory, i.e. changes to settings are lost when power supply is
lost.

Update

Outdoor

module 

Loads software into the outdoor unit module. The heat pump will not work until a
valid software is loaded

Outdoor

module no

software 

Oudoor   unit   module   has   not   software.   Heat   pump   will   not   work   until   a   valid
software is loaded

Disconnected

TCO  

Failure in thermosensor at the compressor outlet. It is disconnected or turned-off.
The heat pump stops working but can be switched on again after the fault has
been repaired. 

TCO short

circuit 

Failure in thermosensor at the compressor outlet. There is a short circuit. The
heat pump stops working but can be switched on again after the fault has been
repaired.

Disconnected

TEV 

Failure in the thermosensor of evaporator. It is disconnected or turned off. The
heat pump stops working but can be switched on again after the fault has been
repaired.

TEV short

circuit

Failure in the thermo-sensor of evaporator. There is a short circuit. The heat
pump   stops   working   but   can   be   switched   on   again   after   the   fault   has   been
repaired.

Disconnected

TCI 

Failure in the thermo-sensor at the compressor inlet. It is disconnected or turned
off. The heat pump stops working but can be switched on again after the fault
has been repaired.

TCI short

circuit

Failure in the thermo-sensor at the compressor inlet. There is a short circuit. The
heat pump stops working but can be switched on again after the fault has been

23

Summary of Contents for HPWH 120

Page 1: ...HEAT PUMP WATER HEATER 120 and 150 intended for wall mounting TECHNICAL DESCRIPTION INSTALLATION USE AND MAINTENANCE INSTRUCTIONS v20190723...

Page 2: ...kage into the atmosphere ATTENTION The connection of the indoor unit with a built in heat exchanger to the heat supply system solar and or other water heating systems using water or an aqueous solutio...

Page 3: ...and thus heats water Energy is extracted directly from the air A small amount of electricity is required to operate the compressor Heat pumps are made up of two parts an outdoor unit with a compresso...

Page 4: ...r tanks of the appliances are suitably protected against corrosion by means of a high quality enamel coating or high alloy chromium nickel steel Enamelled water tanks incorporate special alloy anodes...

Page 5: ...on of the installation and the connection of the heat exchanger of the water heater to it shall be performed only by qualified and competent companies with such subject of activity and in accordance w...

Page 6: ...he wall with the most suitable position with enough space to simplify the installation and maintenance of the outdoor unit Figure 1 b The outdoor unit shall be installed on a load bearing wall or non...

Page 7: ...e the shortest and as simple as possible way max 8 m long and 3 m elevation gain WARNING This is one of the conditions for the validity of the warranty d Protect pipes and cables to prevent damage ATT...

Page 8: ...system e Place the insulation on the pipes as first closing their openings in order to prevent any contamination getting inside them f Place the brass nuts on the pipes in the correct direction and m...

Page 9: ...1 4 Approximately 150 200 kgcm 15 20 Nm 9 52 mm 3 4 Approximately 350 400 kgcm 35 40 Nm Fig 8 CONNECTING OF THE REFRIGERANT PIPES WITH THE OUTDOOR UNIT Remove the protective plastic cover from the ou...

Page 10: ...age with a suitable detector Fig 11 CONNECTING OF THE INDOOR UNIT TO THE PLUMBING INSTALLATION Fig 12 The plumbing installation to which the indoor unit will be connected as well as the other elements...

Page 11: ...indoor unit to the plumbing system its water tank must be filled with water This is done in the following order Opethn the hot water tap on the farthest mixing cock Open the shut off valve 4 of Figur...

Page 12: ...y the company that has designed the project for installation and connecting the indoor unit It is imperative to install all equipment provided and or recommended by it in regard to safety control and...

Page 13: ...re the protective earth conductor if the cord is released from its attachment After connecting the appliance to the electrical system it is necessary to check its functionality WARNING Failure to comp...

Page 14: ...r 2 upper 15 Indoor unit 16 Magnesium anode 17 Thermal switch 18 Communication cable to the outdoor unit 19 Heater 20 Power supply of the appliance 21 Flange bracket 22 Wi Fi module optional 23 Solar...

Page 15: ...sconnected terminals The power supply cable to the UPS is connected to the terminals Lout phase and Nout zero The output of the UPS is connected to the terminals Lin phase and Nin zero WARNING It is i...

Page 16: ...el coating should not be removed but only wiped with dry cotton cloth without the use of rigid tools Regular removal and cleaning of limestone is essential for the reliability of the appliance It is d...

Page 17: ...special valve is integrated in the combined valve which in normal operation of the indoor unit allows the water expanded during its heating not to drip through the side opening of the valve but to en...

Page 18: ...es 8 Information field 9 Air temperature around the heat pump 10 Heat pump When the heat pump is switched on the blade moves Main screen appliances with heat exchanger 1 Additional features of the boi...

Page 19: ...f the solar If the solar thermal sensor does not work the solar circulation pump will be switched on continuously to avoid overheating of the solar installation Vacation The boiler is in a manually ac...

Page 20: ...the graphs with the average water temperature at the top of the boiler The first three types of graphics are for the last 4 days and the average temperature graphs are for the last 2 days These chart...

Page 21: ...inlet temperature 3 Position of EEV 4 Supply voltage 5 Current 6 Power Consumption 7 Evaporator temperature 8 External ambient temperature 9 Heat pump condition 10 Compressor condition 11 Fan conditio...

Page 22: ...ng the day Vacation Mode Freeze protection solar Activated mode for protection of the solar panel against freezing Freeze protection boiler Activated mode for protection of the boiler against freezing...

Page 23: ...t Damaged Flash A malfunction of the microcontroller resulting in the failure to record the settings in the non volatile memory i e changes to settings are lost when power supply is lost Update Outdoo...

Page 24: ...red The heat pump stops working until the voltage has reached the allowable range High current Current exceeds 7 5A The heat pump stops but can be switched on again after the compressor re start prote...

Page 25: ...all the necessary adjustments to the parameters in the selected menu are made pressing the On Off Back button goes to the previous screen WARNING If you do not change anything for a longer period bet...

Page 26: ...p will switch on regardless of the differential temperature The pump will shut off if the water temperature in the water heater exceeds 85 C Overheating protection at the top of the boiler If the temp...

Page 27: ...when the desired temperature can not be achieved with other heat sources for example at a set temperature above the heat pump maximum allowable or if there is another problem with the heat pump operat...

Page 28: ...by the heat pump and the electric heater The set temperature adjustment ranges are from 20 to 75 C When setting a temperature that exceeds the heat pump allowance the heating is done only with the ele...

Page 29: ...t reduction in electricity costs a low temperature can be set from the Temperature Setting and only in the required time intervals via the timer to switch on the heat pump forcedly and or the electric...

Page 30: ...ghtness of the display Field Anode will define the presence of Anode Protection if the boiler is made of stainless steel there is no anode protection The Power field adjusts the power of the power hea...

Page 31: ...nterrupted its clock is maintained for up to 24 hours If the power is turned off for an extended period of time the clock stops and the next time it is turned on it must be reset WARRANTY WARRANTY TER...

Page 32: ...hange of the shape dimensions and location of parts and components that are exposed to an impact which is not in accordance with its normal use Lost profits tangible and intangible damages caused by t...

Reviews: