10/2016 - Art. Nr. 4200 1016 3901A
24
Function
Automatic combustion control unit TCG 1xx
without TC function
Pressing and
holding the
R
button for ...
... leads to ...
… 1 second...
Unlocking of the
control unit
... 2 seconds....
Locking of the
control unit
... 9 seconds.... Clearance of control
unit statistics
The TCG 1xx automatic gas combustion
control unit controls and monitors the forced-
draught burner. The microprocessor-
controlled programme sequence ensures
maximum stability of time periods, regardless
of fluctuations in the power supply or ambient
temperature. The automatic combustion
control unit is designed to cope with
brownouts, guaranteeing system operation
even in the event of extreme power failures.
Whenever the supply voltage drops below its
rated minimum level, the control unit shuts
down - even in the absence of a malfunction
signal. The control unit switches itself back on
again once the voltage has returned to
normal levels.
Locking and unlocking the system
The control unit can be locked (switched to
malfunction) and unlocked (malfunction
cleared) by pressing the
R
reset button,
provided the system is connected to the
mains power supply.
Always disconnect the power supply
before installing or removing the
control unit. Do not attempt to open or
carry out repairs on the control unit.
A4
display
BP1
push-button 1
Request: fault code
BP2
push-button 2
Request: values
Symbol
Designation
Waiting for heat request
Waiting for air pressure switch during burner start
Burner motor on
Ignition transformer on
Flame present
1:
No voltage
2:
No heat request when the power is
on
3:
Heat request, checking rest status
of the air pressure switch
4:
Motor powered, air pressure check
5:
Pre-ventilation
5':
Pre-ignition, activation of unau-
thorised flame monitoring
6:
Flame formation, safety time
7:
Post-ignition time
8:
Operation
9:
Burner shutdown
10:
Regulator shutdown
VG1