02/2016 - Art. Nr. 4200 1046 8202A
8
Operation
Terminal allocation chart
230 Volt connection
Earth
Pre-heater
Flame
monitor
Fault
display
Air
pressure
switch
Ignition
Blower motor
2nd stage
solenoid valve
Connector
Terminal
Terminal
Connector
Remote
unlocking
L1 power
supply
1st stage
solenoid valve
3rd stage
solenoid valve
2nd stage
thermostat
Heating
request
Earth
Fuel oil
pump motor
Terminal
Description
Connector
Terminal
Description
Connector
1
Burner motor live
4
1
Flame detector signal
11
2
Earth
2
Neutral conductor
3
Neutral conductor
3
Live
4
1st stage solenoid valve live
1
4
Live
10
5
Earth
5
Air pressure switch signal
6
Neutral conductor
6
Live
20
7
2nd stage solenoid valve live
2
7
Remote unlocking signal
8
Earth
8
Neutral conductor
21
9
Neutral conductor
9
Malfunction signal live
10
3rd stage solenoid valve live
3
10
Live
25
11
Earth
11
Pre-heater/authorisation contact
12
Neutral conductor
12
Earth
13
Ignition transformer live
5
13
Neutral conductor
14
Earth
14
Live L1
6
15
Neutral conductor
15
Earth
16
2nd stage thermostat live (T6)
T6/7/8
16
Neutral conductor
17
Signal T7
17
Earth
18
Signal T8
18
Earth
19
1st stage thermostat live (T1)
19
19
Fuel oil pump live
35
20
Heating request signal (option T2)
20
Earth
21
Neutral conductor