Servicing
Fault diagnosis menu
Operating statistics menu
Fault diagnosis menu
To access the fault diagnosis menu, press any key when the burner is ready to operate, already
operating, or in malfunction mode. It is not possible to access the fault diagnosis menu during the
start-up phase.
The general menu screen will appear. Using the
,
,
, or
keys, place the cursor on the
fault diagnosis menu symbol, and confirm using the
key.
The details of the last fault to appear are indicated by the flashing symbol. The flame intensity,
network voltage, the fan speed, number of burner start-ups as well as the operating time of the
burner at the time it switched to malfunction mode are displayed underneath.
Using the
and
keys, it is possible to call up the details of the last 5 faults to have appeared
(the fault number is displayed in the upper left corner of the display).
After the details of the last 5 faults, the telephone number of the after-sales department as well
as the maintenance contract number are shown (no values are entered in the factory).
• Exit the menu using the
key.
Entering a telephone number for the maintenance company and the maintenance contract
number
When the corresponding symbol appears on the display:
• Keep the
key held down until the first figure starts to flash (a short press will exit the menu).
• Using the
or
keys, change the figure to the value required (underscore = empty field)
• Using the
key, move on to the next figure.
• When the number is complete, save using the
key.
Operating statistics menu
To access the statistics menu, press any key when the burner is ready to operate, already
operating, or malfunctioning. It is not possible to access the statistics menu during the start-up
phase.
The general menu screen will appear. Using the
,
,
, or
keys, place the cursor on the
statistics menu symbol, and confirm using the
key.
The statistical data menu comprises 7 screens. You can navigate between the different screens
using the
and
keys.
- Flame detection time for last burner start-up
- Average flame detection time for the last 5 burner start-ups
- Total number of burner start-ups
- Total number of faults
- Total number of operating hours
- Total number of operating hours in 2nd stage