02/2016 - Art. Nr. 4200 1046 8202A
5
en
Display
Description
Display
Description
Waiting for boiler heating
request
The ventilation speed
decreases until it reaches the
setting value for the ignition
position
Waits for pre-heater
Oil valve is opened,
safety time
The ventilation speed increases
until it reaches the setting value
for pre-ventilation
Flame is present, awaiting
authorisation of regulation
Pre-ventilation and pre-ignition
Burner in operation. The lower
line shows the strength of the
flame signal and the operating
time of the burner
Pressing and
holding the
unlocking button
for...
… causes ….
... 1 second ...
the control and
safety unit to unlock.
... 2 seconds ...
the control and
safety unit to lock
... 9 seconds ...
Deleting the control
unit statistics
Operation
TCH 24x control unit
The TCH 24x fuel oil automatic
combustion control and safety unit
controls and monitors the forced draught
burner. The microprocessor-controlled
program sequence ensures maximum
stability of time periods, regardless of
fluctuations in the power supply or
ambient temperature. The control and
safety unit is equipped with a device to
protect against the effects of brownouts.
Whenever the supply voltage drops below
its rated minimum level (< 185V), the
control unit shuts down - even in the
absence of a malfunction signal. The
control unit switches itself back on again
once the voltage has returned to normal
levels (> 195V).
Moves the cursor upwards
Moves the cursor downwards
Increases the marked value
Reduces the marked value
Modifies/confirms the value shown
Unlocks the control and safety unit
Red LED (flashes if failure occurs)
Locking and unlocking
The control unit can be locked using the
release knob
or unlocked as long as
the unit is powered on.
Always switch off the power supply
before installing or removing the
control unit. Do not attempt to
open or carry out repairs on the
control unit.