02/2016 - Art. Nr. 4200 1046 8202A
22
Commissioning
Menu 5: Configuration for domestic use
Adjustment release waiting time
• Activate the setting mode using the
key. The time starts to flash.
• Use keys
,
to decrease or increase the adjustment release waiting time by 1s steps.
Adjustment range 0s-255s.
• Confirm the setting by pressing the
key.
Note: Set the adjustment release to a value of 180s in the boiler STRATON L.
Fan speed when the burner is off (= permanent ventilation**)
• Activate the setting mode using the
key. The setting value starts to flash.
• Use keys
,
to decrease or increase the setting value by 1% steps. Setting value
20%-100%.
• Confirm the setting by pressing the
key.
Note: Do not adjust fan speed higher than 2d stage.
Fan speed during the pre-ventilation phase
As with the fan speed, the setting is carried out when the burner is off. But the set speed should
never be lower than the speed of the 2nd stage.
Note: Same setting as for 2d stage.
Post-ventilation => only accessible if permanent ventilation is deactivated
• Activate the setting mode using the
key. The cursor starts to flash.
• Start or stop post-ventilation using the
,
keys. Time indication at initial start = 5s
(= min value).
• Set post-ventilation time using the
,
keys (max 255s**).
• Confirm the setting by pressing the
key.
Fan speed during the post-ventilation phase
During the post-ventilation phase air pressure is monitored. Therefore set post-ventilation speed
≥
speed of 1st stage.
A value < 20% causes a lockout, because the fan stops.
• Activate the setting mode using the
key.
• Decrease or increase the speed using the
,
keys.
• Confirm the setting by pressing the
key.
Note: In the boiler STRATON L set post-ventilation to a value of 30s. This setting also
applies to the other types of condensation boilers.
** As the fuel-pump motor is not in operation during the permanent ventilation and
post-ventilation phases, there is no need to install an additional fuel-oil solenoid
valve.