20
End of the "Setting with flame" menu
The burner setting is now complete. If necessary, it is possible to again correct each of the
settings values. To do this, position the cursor on the value
to be modified, using the
or
key.
Otherwise, the
"Setting the flame"
menu can be closed using any of the methods below, at any
time:
- Restart the burner setting procedure, passing through the presetting phase (without entering a
password). To do this, position the cursor on the
symbol and confirm with the
key. All
the settings values saved before this time remain available.
- Saving the fixed values and ending the setting procedure. To do this, position the cursor on the
symbol and confirm with the
key. The burner is now ready to operate and can be
controlled by the boiler regulation.
- Exiting the settings menu without reaching the end of the setting procedure. To do this, position
the cursor on the
symbol and confirm with the
key. All the speed settings saved at the
time will be recovered when the setting menu is next called up.
Operating mode - Display of the operating status, the flame signal and the operating time
After setting of the burner has been completed, it switches to operating mode.
The current operation of the burner (Operation in 1st or 2nd stage) is indicated by the light bar.
The lower left cell shows the intensity of the flame signal. The display range is from 0 µA to 13
µA. A good quality signal is above 3µA.
The following limit values are valid:
• During the unauthorised flame test, the signal must be < 0.7µA
• During the safety time, the signal must be > 1.3 µA
• During operation, the signal must be > 1.1µA
The cell at the bottom right displays the burner's current operating time.
Commissioning
Setting with flame
Operating mode