![elco THISION L PLUS Operating Manual Download Page 70](http://html1.mh-extra.com/html/elco/thision-l-plus/thision-l-plus_operating-manual_2377082070.webp)
70
Operation
Parameter listing
Menu
Submenu
Parameter Name
Description
Range
Factory
settings
26..32. Commercial Boiler - Slave 1..
26..32. 0
General
26..32. 0.
0
Engines Number
26..32. 0.
2
Maximum Water temp
°C
95
26..32. 0.
3
Max CH Adjustable
%
100
26..32. 0.
4
Fan inc percentage
4
26..32. 0.
5
Altitude
m
0
26..32. 0.
6
Boiler tank solar integration
0
26..32. 0.
7
Emergency setpoint
°C
45
26..32. 3
Water Circulation
26..32. 3.
0
Max PWM Pump
%
95
26..32. 3.
2
Min PWM Pump
%
45
26..32. 3.
3
CH pump overrun
min
5
26..32. 5
Domestic Hot Water
26..32. 5.
0
DHW Setpoint Temperature
40 - 65°C
65
26..32. 5.
1
Comfort Function
0 = Disabled
1 = Time Based
2 = Always Active
0 - 2
0
26..32. 5.
2
System DHW Mode
0 = CH Only
1 = DHW Tank NTC
2 = DHW Tank Thermostat
0 - 2
0
26..32. 5.
3
Boiler DHW Mode
0 = CH Only
1 = DHW Tank NTC
2 = DHW Tank Thermostat
0 - 2
0
26..32. 5.
4
Anti-legionella Function
0 = OFF
1 = ON
0 - 1
0
26..32. 5.
5
Boiler DHW Charging Type
0 = Recharging
1 = Full charging
2 = Full charging Legio
0 - 2
0
26..32. 5.
6
System DHW Charging Type
0 = Recharging
1 = Full charging
2 = Full charging Legio
0 - 2
0
26..32. 5.
7
Boiler DHW Circulating Pump Release
0 = Release
1 = Time Programs
2 = Circ Pump special Time Programs
0 - 2
0
26..32. 5.
8
System DHW Circulating Pump Release
0 = Release
1 = Time Programs
2 = Circ Pump special Time Programs
0 - 2
0