Operation
Parameter listing
Menu
Submenu
Parameter Name
Description
Range
Factory
settings
4.
2.
2
Slope
LT: From 0.2 - 1.0
HT: From 1.0 - 3.5
0.6LT
1.3HT
Increase setting:
Increases the flow
temperature, especially at low
outside temperatures.
Reduce setting:
Reduces the flow temperature,
especially at low outside
temperatures.
flow temperature
low temperature level
high temperature level
outdoor temperature
room temperature
setpoint
°C
°C
23
23
21
21 19
19
30
20
10
0
40
50
60
70
80
90
°C
5
10
15
20
25
3.5 3.0
2.5
2.0 1.8
1.5
1.3
0.8
1.0
0.6
0.4
0
-5
-10
-15
-20
-25 °C
0.8
0.6
1.0
0.4
0.2
4.
2.
3
Offset
Offset heating line adjustable per °C
LT: From -7°C to +7°C
HT: From -14°C to +14°C
0
0
4.
2.
4
Room influence proportional
Only visible on the boiler if a room sensor
is connected
LT=2
HT=4
4.
2.
5
Max T
Zone 1 Maximum Flow Temperature
LT: From 20°C to 45°C
HT: From 20°C to 85°C
45°C
85°C
4.
2.
6
Min T
Zone 1 minimum Flow Temperature
LT: From 20°C to 45°C
HT: From 20°C to 85°C
25°C
20°C
4.
2.
7
Thermo regulation logic
0 = OFF, 1 = ON
0 - 1
0
4.
2.
8
Quick night setback
0 = OFF, 1 = ON
0 - 1
0
4.
2.
9
Heat request mode
0 = Standard
1 = RT Time Programs Exclusion
2 = Forcing Heat Demand
0 - 2
0
4.
3
Zone1 Diagnostics
4.
3.
4
Heat Request Z1
0 = OFF, 1 = ON
4.
3.
9
Heating rate
0 = OFF, 1 = ON
5
Zone2 Parameters (see Zone1, chapter 4)
6
Zone3 Parameters (see Zone1, chapter 4)