Installation
Connections
Air- / flue gas ducts - installation variants for multiple boilers
Opting for a collective flue gas outlet
is determined by:
-
The position of the boilers with
regard to their outlet area
- Sufficient space above the boilers
-
Large number of boilers
You may opt for:
- Collective flue gas outlet
under-pressure
- Collective flue gas outlet
over-pressure
In many situations, flue gases cannot
be vented individually because the
installation is indoors. For such
situations, we recommend collective
venting by means of under-pressure or
over-pressure using a flue gas outlet
system. The air supply may also be
supplied collectively, but if the boiler
room is suitable for that purpose it may
also be obtained from this area (`open
device` Boiler category B).
If you install a common duct providing
combustion air to more than one
appliance, there is a risk that
combustion air would be drawn from an
adjacent appliance.
This may then be subject to a
negative pressure.
In the case of collective venting
of flue gases, the flue gas-venting
outlet always has to end up in the
open area (outlet area 1).
ELCO can supply a collective flue gas
outlet system for the ELCO THISION L
PLUS. Refer to the following chapters
with regard to the various possibilities
and maximum pipe lengths that can
be used.
0,2 x
2 x B
Boiler category: B
Outlet area 1
(free outlet area)
Boiler category: C
Permitted only when the air
intake and the flue gas
outlet are in the same
pressure area