Operation
Parameter listing
Menu
Submenu
Parameter Name
Description
Range
Factory
settings
24 Commercial Boiler
24. 0
General
24. 0.
2
Maximum Water temp
20 - 95 °C
95
24. 0.
3
Max CH Adjustable
0 - 100 %
100
24. 0.
4
Fan inc percentage
4 - 400 %
4
24. 0.
5
Altitude
0 - 3000 m
0
Boiler tank solar integration
0 = Absent
1 = Present
0 - 1
0
24. 0.
7
Emergency setpooint
20 - 90 °C
45
24. 3.
Water Circulation
24. 3.
0
Max PWM Pump
61 - 95 %
95
24. 3.
1
Min PWM Pump
20 - 95 %
46
24. 3.
2
CH pump overrun
0 - 10 min.
5
24. 5
Domestic Hot Water
24. 5.
0
DHW Setpoint Temperature
40 - 65 °C
65
24. 5.
1
Comfort Function
0 = Disabled
1 = Time Based
2 = Always Active
0 = 2
0
24. 5.
2
System DHW Mode
0 = CH Only
1 = Storage with NTC
2 = Storage with Thermostat
0 - 2
0
24. 5.
3
Boiler DHW Mode
0 = CH Only
1 = Storage with NTC
2 = Storage with Thermostat
0 - 2
0
24. 5.
4
Anti-legionella Function
0 = OFF, 1 = ON
0
0 = OFF
1 = ON
24. 5.
5
Boiler DHW charge mode
0 - 2
0
0 = Charge
1 = Full charge
2 = Full charge Legio
24. 5.
6
System DHW charge mode
0 - 2
0
0 = Charge
1 = Full charge
2 = Full charge Legio
24. 5.
7
Boiler DHW Circulating Pump Release
0 - 2
0
0 = Release
1 = Time Program
2 = Special Time Program