Technical Data
AEROTOP G07 / G10 / G12 / G07-14M
Series
AEROTOP G
Model
G07
G10
G12
G07-14M
Energy efficiency category, average
climate, W55/W35
1)
A++/A++
A++/A++
A++/A++
A++/A++
Power regulation
No
Yes
Heating
(2)
Capacity range min-max
A7/W35
[kW]
8.64
12.52
14.1
4,7 - 17,5
Nominal heating capacity
[kW]
8.64
12.52
14.1
11.0
Nominal power input
[kW]
1.85
2.69
3.33
2.2
COP
4.65
4.65
4.23
5.0
Capacity range min-max
A2/W35
6.36
9.22
11.8
3,6 - 15,2
Nominal heating capacity
[kW]
6.36
9.22
11.8
10.0
Nominal power input
[kW]
1.72
2.5
3.24
2.6
COP
3.69
3.69
3.64
3.8
Capacity range min-max
A-7/W35
5.30
7.60
10.30
2.9 - 12.7
Nominal heating capacity
[kW]
5.30
7.60
10.30
10.7
Nominal power input
[kW]
1.70
2.50
3.10
3.6
COP
3.10
3.10
3.30
2.9
Capacity range min-max
A-7/W55
2,9 - 12,8
Nominal heating capacity
[kW]
5.00
7.30
9.80
10.8
Nominal power input
[kW]
2.40
3.50
4.40
5.7
COP
2.10
2.10
2.20
1.9
Evaporator, air side
Evaporator
Grooved copper pipes and fins in hydrophilic aluminium
Fan
Axial
Air flow min-max
[m³/h]
3500
4000
4600
2800-5200
Available static pressure (without
Pa
47
45
41
34-55
Min external air temperature in hea-
[°C]
-18
Max external air temperature in hea-
[°C]
35
Condenser, water side
Nominal water flow (dT=5K)
(2)
A2/W35
[m³/h]
1.52
2.09
2.80
1.93
Nominal pressure drop (dT=5K)
[mbar]
128
218
350
250
Minimum water flow
[m³/h]
0.76
1.08
1.37
0.97
Circulator model
YONOS PARA 25/7.5
STRATOS
PARA 25/1-
9
YONOS PARA
25/7.5
Available pressure head
[mbar]
576
370
254
382
3-way water valve integrated
No
Max operating pressure
[bar]
3
Plate heat exchanger material
AISI 316
1)
Note on the energy efficiency category: This information complies with the official requirements for room heaters (EU regulation no. 811/2013) that will
be mandatory as of September 2015, based on the data for heating heat pumps as per EN 14511 and EN 14825.
2)
According to EN 14511, EN 14825According to EN 14511, EN 14825
9
Summary of Contents for AEROTOP G
Page 28: ...Installation Delivery to installation site 2 3 1 n 17 4x 8x M10 4x 4x 28...
Page 29: ...Installation Delivery to installation site 29...
Page 31: ...Installation Hydraulic connections assembly instructions 3 1 n 3 1 4 2x n 46 1 x 2 1 4 10 x 31...
Page 32: ...Installation Hydraulic connections assembly instructions 4 7 5 8 4x 1 4 6 2 x 32...
Page 36: ...Installation Instruction for the installation of control unit black wire CL 5 4 36...
Page 57: ...Notes 57...
Page 58: ...Service www elco net...