Installation
Hydraulic connections
Hydraulic connections to the
heating system
The heater flow and return lines must
be kept as short as possible and well-
insulated in order to avoid heat loss.
The hydraulic connections should be
made with flexible ducts in order to
avoid broken ducts and the transmis-
sion of structure-borne noise
through the distribution network to
the radiators.
The ductwork must be carried out in
such a way that pressure drops at the
nominal volume flow do not exceed
the available pressure since this
would reduce the output of the heat
pump.
This means that ducts cannot have
elbows that are too narrow.
The optional pre-assembled trans-
mission line allows the machine to be
connected quickly and securely.
It consists of a sound-insulated, flexi-
ble duct which contains
•
Flow and return pipes for the
heater
•
Condensation drainpipe
•
Conduit to accommodate electri-
cal cable.
Dimensions
Heater flow pipe
Ø 1” flexible.
Heater return pipe
Ø 1” flexible.
Each heat pump has defined stand-
ard hydraulic diagrams. Integration in
accordance with these various
diagrams will ensure trouble-free and
safe operation.
Before making hydraulic connec-
tions, the entire pipeline system of
new as well as retrofitted systems
must be thoroughly flushed.
Residue left in the heater pipes will
damage the heat exchangers and
cause the heat pumps to malfunction.
It is recommended that a dirt filter be
installed in the heater return line,
especially if no buffer storage is
present.
A
Ansicht von unten
Temperature range
°C
from - 30 up to +
95
Corrugated stainless steel tube
DN 32
Material
1.4404
Maximum allowable working pressure
bar
6,5
Maximum allowable pressure for leak checks
Bar
4,8
Volume of liquid in corrugated tube (the double for meter)
l/m
2,13
Cladding tube
Outer diameter
mm
200
Maximum radius of curvature
mm
500
Maximum diameter of the connector to the wires of the con-
trol circuit and the sensor
mm
45
Ring stiffness according to DIN 16961 ( row of tubes 4 )
kN/m²
SR
24
≥
16,0
Conduit to accommodate electrical cable.
Outer diameter
mm
32
Inner diameter
mm
22
Insulation material EPDM closed cell
Class of building material according to DIN 4102
B2
Reference value of the thermal conductivity to + 40 ° C
W/mK
λ
40°C
= 0,037
Reference value of the thermal conductivity to 0 ° C
W/mK
λ
0°C
= 0,033
Insulation thickness hot water outlet pipe / Water return pipe
from the system
mm
25 / 19
Pressure Drop
Pr
e
s
s
u
re
D
ro
p
p
e
r
m
e
te
r
Flow rate (m
3
/h)
Average Temperature
Pressure drop coefficient for water
Pressure drop coefficient for mix water and
Tyfocor L 70/30
B
30
Summary of Contents for AEROTOP G
Page 28: ...Installation Delivery to installation site 2 3 1 n 17 4x 8x M10 4x 4x 28...
Page 29: ...Installation Delivery to installation site 29...
Page 31: ...Installation Hydraulic connections assembly instructions 3 1 n 3 1 4 2x n 46 1 x 2 1 4 10 x 31...
Page 32: ...Installation Hydraulic connections assembly instructions 4 7 5 8 4x 1 4 6 2 x 32...
Page 36: ...Installation Instruction for the installation of control unit black wire CL 5 4 36...
Page 57: ...Notes 57...
Page 58: ...Service www elco net...