OPERATION
NP-DK50 2V 50, 2x2V 110-AD-A-1_03-2022
52
03/2022
OPERATION
ONLY TRAINED PERSONNEL MAY OPERATE THE EQUIPMENT!
Risk of electric shock.
In case of emergency, disconnect the compressor from the mains (pull out the
mains plug).
Burn or fire hazard.
Portions of the air pump and compressed air components between the air pump
and the dryer may be hot and reach hazardous temperatures during
compressor operation that may harm materials or operating staff.
Warning
– compressor is controlled automatically.
Automatic start-up. When pressure in the pressure tank drops to switch-on
pressure, the compressor automatically switches on. The compressor
automatically switches off, when pressure in the air tank reaches the switch-off
pressure.
Potential for damage to pneumatic components.
The working pressure settings for the pressure switch set by the manufacturer
cannot be changed. Compressor operation at a working pressure below the
switching pressure indicates high air usage (see the Troubleshooting chapter).
Required drying performance can only be achieved when following the defined
operating conditions.
Drying performance will decline and the achieved dew point will drop if the dryer
is operated at any pressure below the minimum working pressure.
During prolonged operation of the compressor, the ambient temperature around
the compressor may increase to over 40 °C. At this point the cooling fan
automatically switches on. The fan switches off once the space is cooled to
around 32 °C.
Summary of Contents for DK50 2V/50/M
Page 1: ...N VOD NA POU ITIE SK USER MANUAL EN BENUTZERHANDBUCH DE...
Page 2: ......
Page 4: ...CONTENTS 5 INHALT 76 OBSAH 146...
Page 18: ...PRODUCT DESCRIPTION NP DK50 2V 50 2x2V 110 AD A 1_03 2022 18 03 2022 B DK50 2x2V 110S M...
Page 89: ...PRODUKTBESCHREIBUNG 03 2022 89 NP DK50 2V 50 2x2V 110 AD A 1_03 2022 B DK50 2x2V 110S M...
Page 158: ...POPIS V ROBKU NP DK50 2V 50 2x2V 110 AD A 1_03 2022 158 03 2022 Obr 4 Skrinka A DK50 2V 50S M...
Page 159: ...POPIS V ROBKU 03 2022 159 NP DK50 2V 50 2x2V 110 AD A 1_03 2022 B DK50 2x2V 110S M...
Page 218: ......
Page 219: ......
Page 220: ...NP DK50 2V 50 2x2V 110 AD A 1_03 2022 112000519 000...