21.3. Alarm conditions
Low / high pressure
A red warning is shown (“Warning!”) if low pressure (<3 bar)
or high pressure (> 8.5 bar, or > 10.5 bar depending on the
pressure version) is detected. At the same time, the current
pressure tile lights up red.
The warning is displayed as long as the alarm condition
endures.
A list of warnings is saved in the “Warning log”
The dryer is not operating normally, regeneration is not initiated,
the compressor must be shut down
A high dew point alarm may
appear when the unit is first
placed into service. The alarm
will persist until the dryer
regenerates. The regeneration
time of the dryer depends on
many parameters of use of the
device.
Dryer
regeneration
should take no more than 24
dryer working hours. If the
dryer cannot meet the dew
point set-point during the first
24
hours,
please
contact
service personnel.
21.4.
„Call Service“ screen
The “Call Service” screen alternates with the main screen if a
notification or warning occurs.
Summary of Contents for DK 50 4X2VT/M
Page 1: ...DK50 4x2VT M DK50 6x2VT M USER MANUAL EN...
Page 2: ......
Page 13: ...PRODUCT DESCRIPTION 06 2022 13 NP DK50 Nx2VTM ADM EN 1_06 2022 Fig 2 Adsorption dryer...
Page 24: ...INSTALLATION NP DK50 Nx2VTM ADM EN 1_06 2022 24 06 2022 Fig 5 Handling the compressor module...
Page 31: ...INSTALLATION 06 2022 31 NP DK50 Nx2VTM ADM EN 1_06 2022 15 PNEUMATC DIAGRAMS DK50 4x2VT M...
Page 32: ...INSTALLATION NP DK50 Nx2VTM ADM EN 1_06 2022 32 06 2022 DK50 6x2VT M...
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ...NP DK50 Nx2VTM ADM EN 1_06 2022 112000595 0001...