Application manual
KNX binary output modules EK-GA1-TP
Release 1.5 - Update: 02/2022
MAEKGA1TP_EN
© EKINEX S.p.A. - All rights reserved
Page 25
6.4.6.7
Scene management
Each output can be linked to up to 8 scene codes; when one of these scene codes is recalled through a bus
command originated by any controller device, the output will assume a preset value (which includes both the
On
– Off status and the dimming value). An additional delay can be defined for the output activation (or
deactivation) from the moment the scene code is recalled.
The output value for a scene can either be fixed and chosen in the configuration phase, or it can be defined
as reprogrammable through a Scene Learning command.
If this latter option is enabled (for each single output), whenever a Scene Learning command is received on
the bus for a specific scene code to which the output has an association, the device will store the current
output status value for that scene. This value will then be recalled in subsequent scene activations.
Fig. 14 - Scene store / recall command code