The light is activated by a “start” command (e.g. through a pushbutton or a presence sensor), and
normally remain lit for a programmed time duration;
There is a provision to enable a “stop” (Manual Off) command, again through a pushbutton or other
events, that allows to switch the light off before the programmed time expires (e.g. because the
person who triggered the presence sensor has surely left the building through an exit);
There is a provision to allow another “start” command (Retriggering), received during activation, to
restart the time duration counter;
A further optional “pre-warning” function allows to briefly switch off the load a certain time before
expiration (both times, i.e. pause duration and time before expiration, are configurable) in order to
warn the user that the activation time is about to end.