Application manual
KNX binary output modules EK-GA1-TP
Release 1.5 - Update: 02/2022
MAEKGA1TP_EN
© EKINEX S.p.A. - All rights reserved
Page 38
7 Appendix
7.1 Communication objects table
Following is a summary of all KNX Communication Objects (CO) and corresponding Data Point Types (DPT)
defined by the application program according to configuration options.
The listing order is generally by CO number.
Object name
Conditions
Size
Flags
DPT
CO number(s)
Disable front pushbuttons
Manual operation = enabled
Disable from bus = yes
1 bit
C-W--
[1.002] boolean
0
Power off alarm
Device power off alarm =
enabled
1 bit
CR-T-
[1.005] alarm
1
Output X
–
On/off Command
Channel
x
=
enabled /
copy parameters from...
1 bit
CRWTU
[1.001] on/off
2, 24
Standard “handle” for switching the output through a bus command.
Output X
–
Dimming command
Channel
x
=
enabled /
copy parameters from...
2 bit
C-W--
[3.007] Dimming
control
3, 25
Control point for relative (i.e. up / down) dimming.
Output X
–
Absolute setpoint control
Channel
x
=
enabled /
copy parameters from...
8 bit
unsigned
C-W--
[5.001]
Percentage
0..100%
4, 26
Control point for setting the absolute dimming value.
Output
x
–
On off status
Status feedback telegram =
enabled
1 bit
CR-T-
[1.001] switch
5, 27
Sent at any change of the output state and also periodically, as configured.
Not sent when activated manually through maneuvering lever.-
Output
x
–
Actual dimming value
Status feedback telegram =
enabled
8 bit
unsigned
CR-T-
[5.001]
Percentage
0..100%
6, 28
Sent at any change of the output state and also periodically, as configured.
Output
x
–
Staircase lighting
start stop command
Staircase lighting function =
enabled
1 bit
C-W--
[1.001] on/off
7, 29
Starts the staircase light timing with an On value.
The timed activation automatically stops at the end of the preset time.
If “Manual off” is enabled, the communication object will stop the timing with an Off value.
If “Retriggerable” is enabled, the transmission of a new “On” value will restart the timing.
Output
x
–
Lock command
Locking function =
enabled
1 bit
C-W--
[1.003] enable
8,30
Inhibits both the switching and value setting commands for the
output when an “enable” telegram is
received, and unlocks them when a “disable” telegram is received.